Vcc-x configuration, Vcc-x confi guration screens, Vcc-x operator interface sd – Orion System VCC-X Controller User Manual

Page 31

background image

VCC-X Operator Interface SD

VCC-X CONFIGURATION

31

VCC-X Confi guration Screens

Confi guration Screen #33 - Economizer

Voltage Output

VCC-X Cnfg ID #

Econo Voltage Output

Min Volts: 2.0VDC
Max Volts: 10.0VDC

Enter

a value between 0.0 and 10.0 VDC for the Economizer mini-

mum and maximum output voltage. Defaults are 2 VDC Min and
10 VDC Max.

Description

Minimum

Default

Maximum

Min Economizer Voltage

0

2

10

Max Economizer Voltage

0

10

10

Confi guration Screen #34 - CO

2

Sensor

Installed

VCC-X Cnfg ID #

CO2 Sensor Installed

NO

USE < or > TO CHANGE

Select

YES if you have a CO

2

Sensor installed. Default is NO.

Confi guration Screen #35 - Building Pressure

Sensor Installed

VCC-X Cnfg ID #

Building Pr. Sensor

Installed

None

If this unit has a Building Pressure Sensor installed, select Analog if
it is a wired sensor. Select Receive Broadcast if the Building Pres-
sure Sensor is attached to a separate device that will broadcast the
reading, e.g., GPC-XP Controller. Default is None.

Confi guration Screen #36 - Building Pressure

Control

VCC-X Cnfg ID #

Building Pr. Control

None

USE < or > TO CHANGE

Default is None. Available options are:



None

—No Building Pressure Control by this controller.



On/Off Exh Relay

—If an On/Off Exhaust Fan is being

used, select this option and confi gure a relay output as

Exhaust Fan. If the building pressure rises above

setpoint, this relay will energize. This is Direct-Acting

control.



Modulating Exh

—If the building pressure rises above

setpoint, a modulating signal will be used to control an

exhaust fan VFD or a modulating damper to maintain

setpoint. A relay confi gured as Exhaust Fan can be used

to enable this device so that the modulating signal can

control it. This is Direct Acting control.

 

OA Damper

—Select if reverse acting Building Pressure

Control using the Outdoor Air Damper is required. If

the building pressure falls below setpoint, the OA

Damper (Economizer) signal will be used to modulate

the OA Damper to maintain setpoint. This is Reverse

Acting

control.

 

Supply Fan

—Contact WattMaster Factory regarding

this reverse acting Building Control option. This should

not be used in most applications. This is Reverse Acting

control.

Confi guration Screen #37 - Building Pressure

Control Rate

VCC-X Cnfg ID #

Building Pr. Control

Rate: 10 Sec

[ 1 - 30 Seconds ]

Default is 10 seconds. The Building Pressure Control Rate is the
time period between changes to the Building Pressure Control signal.

Confi guration Screen #38 - Building Pressure

Control Max Adjust

VCC-X Cnfg ID #

Building Pr. Control

Max Adjust: 5%

[ 1 - 30% ]

This is the maximum amount that the Building Pressure Control
output can adjust to when it needs to. Default is 5 percent.