VCC-X Operator Interface SD

SYSTEM CONNECTION

7

Modular System Manager SD Network Connection

Network Connection

As previously described, when you are connecting the Modular
System Manager to a Networked System, the Modular System
Manager is connected to the communications and power loop of
the system via modular cables. These cables simply plug into the
System Manager board and to any device with modular connectors
on any local loop on the system. Devices with modular connectors
include the Power/Comm Distribution Board, VAV/Zone controller,
and MiniLink Polling Device. By using these plug-in connections,
wiring errors are virtually eliminated and system installation is fast
and easy. See Figure 4 below for typical connection information.
See Figure 5 on page 8 for typical Power/Comm board wiring and
connection information.

Figure 4: Modular System Manager SD - Network

When the System Manager is to be connected to a Stand Alone
system, a 12-foot cable with modular connectors on one end and
stripped wire ends on the other end is provided for this purpose. This
is used to facilitate connecting communications and power wiring
to the Modular System Manager from a 24 VAC power source and
to the HVAC unit controller communication wiring terminals. See
Figure 6 on page 9 for wiring details. If the supplied cable wire is
not long enough for your installation, a standard modular cable of
the correct length can be purchased through WattMaster and one of
the modular connectors can be cut off to allow for the transformer
and communication terminal wiring connections. It is recommended
that you do not splice the communications wire if at all possible.
The transformer should be rated at 6 VA minimum power output.

All Modular Power/Comm
Cables Are To Be
WattMaster Part Number
PCC-xx Or PCCE-xx
Cables.

Power/Comm Cables To
Power/Comm

Or VAV/Zone Controllers On
Local Loop.

Distribution

Board, MiniLink Polling Device

Modular System Manager SD
Back View

NOTE: For Stand-Alone
Installations (No CommLink
or MiniLink), All TERM
Jumpers Must Be ON.
For All Applications With
CommLink(s) Or MiniLink(s),
All Jumpers Must Be OFF.

4