VCC-X Operator Interface SD

VCC-X SETPOINTS

47

Setpoint Screen #22 - Head Pressure

Setpoints - Cooling and Reheat

VCC-X Spts ID:#

Head Pressure Spts

Cooling: 340psi
Reheat: 390psi

If a Head Pressure Transducer is connected to the RSMV Module
you can control a Condenser Fan or a Condenser Water Valve to
maintain these Head Pressure Setpoints in the Cooling and Dehu-
midifi cation Reheat Modes.

Description

Minimum

Default

Maximum

Cooling Head Pressure
Setpoint

240 PSI

340 PSI

420 PSI

Reheat Head Pressure
Setpoint

240 PSI

390 PSI

420 PSI

Setpoint Screen #23 - Economizer Enable

Setpoint

VCC-X Spts ID:#

Economizer Enable

Setpoint: 72.0ºF

If this unit has been confi gured for Economizer control and an Out-
door Humidity Sensor is not connected to the VCC-X Controller, if
the Outdoor Temperature falls below this setpoint, the Economizer
can be used for free cooling. If a combination Outdoor Air Tem-
perature/Humidity Sensor is connected to the VCC-X Controller and
the Wetbulb or Dewpoint Temperature falls below this setpoint, the
Economizer can be used for free cooling.

Description

Minimum

Default

Maximum

Economizer Enable

-30ºF

(-34.4

º

C)

55ºF

(12.8

º

C)

80ºF

(26.6

º

C)

Setpoint Screen #24 - Economizer Minimum

Damper Position

VCC-X Spts ID:#

Economizer Min

Damper Pos: 10%

The Economizer (OA Damper) Minimum Position Setpoint is
maintained during the Occupied Mode even if the Economizer is
disabled due to the OA Temperature being above the Economizer
Enable Setpoint.

Description

Minimum

Default

Maximum

Economizer Min Position

0%

10%

100%

Setpoint Screen #25 - Maximum Economizer

Position in Heat Mode

VCC-X Spts ID:#

Max Econo Pos In

Heat Mode: 50%

This Setpoint allows you to set the Maximum Position the Outdoor
Air Damper will open to while Heating is operating. This takes prior-
ity over the Economizer Maximum Position in High CO

2

Setpoint.

Description

Minimum

Default

Maximum

Maximum Economizer
Position in Heat Mode

0%

50%

100%

Setpoint Screen #26 - Minimum Outdoor

Airfl ow Setpoint & Deadband

VCC-X Spts ID:#

Min. Outdoor Airflow

Setpoint.: 2.00kCFM
Deadband.: 200CFM

If controlling the Outdoor Air Damper to an airfl ow setpoint, this
screen allows you to set the design Minimum Outdoor Air CFM
Setpoint. The Deadband controls the rate of change for the damper
signal. As OA CFM moves further from setpoint within this window,
the damper makes a larger change.

Description

Minimum

Default

Maximum

Minimum Outdoor
Airfl ow Setpoint

0.10 kCFM

2.00 kCFM

200 kCFM

Deadband

10 CFM

200 CFM

9999 CFM

VCC-X Setpoint Screens