Vav/zone damper force, Vav/zone damper force modes, Vcc-x operator interface sd 78 – Orion System VCC-X Controller User Manual

Page 78: Damper force modes

background image

VAV/ZONE DAMPER FORCE

VCC-X Operator Interface SD

78

VAV/Zone Damper Force Modes

Damper Force Modes

Damper Force Modes are available for testing or balancing the sys-
tem. These Force Modes can be accessed and programmed from
the Modular Service Tool.

Modular Service Tool Instructions

When using the Modular Service Tool, simply press the

ANCE - TEST>

key. You will then see the Unit ID Screen. Enter the

unit ID of the controller you wish to access and press

.

Once communication is established, the *00* message will go away.
Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

The following screen will be displayed:

Damper Force
Para Blocks

Load / Save / Copy

With the cursor on Damper Force,

press to access the

Damper Force Mode Screen.

Dampers Force Mode Screen
If the unit ID you entered is for a VCC-X Controller that has VAV/
Zone Controllers connected to its communication loop, the Damper
Force Mode will act as a “Global” Damper Force Mode. That is, all
VAV/Zone Controllers on that VCC-X Controller’s communication
loop will be forced to the same Damper Force Mode setting. If the
unit ID you entered is for a VAV/Zone Controller, the Damper Force
Mode setting will only apply to that VAV/Zone Controller.

Damper Force

Enter Force Mode: 0
0=Auto 1=Open 2=Clsd
3=Max 4=Min 5=Fixed

Set the appropriate Damper Force Mode by entering numbers 0
through 5. Following is a list of the force modes and their meaning:

0 = Auto

This is the default setpoint. With this setting,

the damper will operate normally and modulate

according to the controller setpoints.

1 = Open

This setting will force the dampers to their

fully-open

position.

2 = Clsd

This setting will force the damper to its fully-

closed

position.

3 = Max

This setting will force the damper to its

Maximum

Position

Setpoint.

See

VAV/Zone

Controller

Setpoint

Screen

#5 on page 73 for

complete

setpoint

information.

4 = Min

This setting will force the damper to its

Minimum

Position

Setpoint.

See

VAV/Zone

Controller

Setpoint

Screen

#5

on page 73 for

complete

setpoint

information.

5 = Fixed

This setting will force the damper to a fi xed

position based on the Fixed Position Setpoint.

See

VAV/Zone Controller Setpoint Screen #8

on page 74 for complete setpoint information.

CAUTION: The Damper Force Modes should only be used

by

qualifi ed service personnel. Serious dam-

age to the ductwork could result if the dampers

are all forced closed and the HVAC unit fan

is

operating.