Troubleshooting, Vcc-x outputs force, Vcc-x operator interface sd 81 – Orion System VCC-X Controller User Manual

Page 81: Outputs force

background image

TROUBLESHOOTING

VCC-X Operator Interface SD

81

VCC-X Outputs Force

Outputs Force

Outputs Force settings are available for testing or troubleshooting the
system. These Force settings can only be accessed and programmed
from the Modular Service Tool.

CAUTION: The Outputs Force settings should only be

applied by qualifi ed service personnel.

Serious damage to the HVAC unit could

result from improper use of these Outputs

Force

settings.

To access the Outputs Force settings, simply press the

- TEST>

button on the Modular Service Tool. You will then see

the Unit ID Screen.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter the unit ID of the VCC-X Controller you wish to access and
press

. Once communication is established, the *00* mes-

sage will go away. Then

press

<

>

. You will then see the screen

shown below. Press

to save entered data and

press

<

>

to scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

NOTE:

The Outputs Force settings are only available for the

VCC-X Controller. They are not supported for the
VAV/Zone Controllers or other Add-on controllers.

Outputs Force

Para Blocks
Save / Load / Copy

Place the cursor on Outputs Force and press

to access the

Outputs Force Screen.

Supply Fan Override
Auto

Use < Or > To Change

The fi rst Outputs Force Screen

allows the AHU fan relay to be set

for Auto, Force On, or Force Off. The default setting is Auto. After
you complete all troubleshooting or testing procedures, all relays
should be changed back to this setting. The Force On setting will
force the relay to the ON (energized) position. The Force Off selec-
tion will force the relay to the OFF (de-energized) position.

The next screen displays the Relay Overrides for Relay 2. After
pressing

to save any changes, press

<

>

to have the

next relay displayed. All 23 Relay Override Screens (including the
AHU fan relay) are available by pressing

<

>

after each setting is

saved by pressing

.

Relay Overrides

Relay 2 Override
Auto

Use < Or > To Change

After the screen for relay 23 is displayed, the fi rst Analog Output
Override Screen

will be displayed.

Analog Output 1 Screen

Main Fan VFD

Override Volts: -1.0

[-1.0 = Auto]

The default setting for normal operation is -1.0 volts. Voltages
between 0 to 10.0 are valid entries. Press

after making

a setting change and then press

<

>

and the next Analog Output

Override Screen

will be displayed.

Analog Output 2 Screen

Economizer

Override Volts: -1.0

[-1.0=Auto]

The default setting for normal operation is -1.0 volts. Voltages
between 0 to 10.0 are valid entries. Press

after making

a setting change and then press

<

>

and the next Analog Output

Override Screen

will be displayed.

Analog Output 3 Screen

Modulating Heat

Override %...: -10%

[-10 = Auto]

The default setting for normal operation is -10 %. Percentages
between 0 to 100 are valid entries. Press

after making

a setting change and then press

<

>

and the next Analog Output

Override Screen

will be displayed.