VCC-X Operator Interface SD

VCC-X CONFIGURATION

37

VCC-X Confi guration Screens

Confi guration Screens #70-76 - VCC-X Relay

Confi guration Screens

VCC-X Cnfg ID #

On-Board Relay (2-8)

Not Used

USE < or > TO CHANGE

Relay #1 is not confi gurable as it is reserved for the Supply Air Fan.
Relays #2-#8 are confi gurable for the following options (See Table
5, page 38
for Relay descriptions):

Not Used (Default)

Cool Stage

Heat

Stage

Mod Heat Enable

Mod Cool Enable

Warmup / Cooldown

ReHeat

PreHeat

Low

Ambient

Exhaust Fan

Economizer

Heat Wheel

Occupied

Mode

Override Mode

Alarm

Active

Relays #2 through #8 can be individually confi gured. Only forms
of Heating and Cooling can be confi gured with multiple relays for
staging. If any other option is selected more than once, it will sim-
ply activate redundant relays, but no multiple staging will occur.
Default is Not Used.

Confi guration Screens #77-81 - EM1 Relay

Confi guration Screens

VCC-X Cnfg ID #

EM1 Relay (1-5)

Not Used

USE < or > TO CHANGE

EM1 Relays #1-#5 are confi gurable for the following options (See
Table 5, page 38 for Relay descriptions):

Not Used (Default)

Cool

Stage

Heat

Stage

Mod Heat Enable

Mod Cool Enable

Warmup / Cooldown

ReHeat

PreHeat

Low

Ambient

Exhaust Fan

Economizer

Heat Wheel

Occupied

Mode

Override Mode

Alarm

Active

Relays #1 through #5 can be individually confi gured. Only forms of
Heating and Cooling can be confi gured with multiple relays for
staging. If any other option is selected more than once, it will simply
activate redundant relays, but no multiple staging will occur. Default
is Not Used.

Confi guration Screens #82-93 - E-BUS

12 Relay Confi guration Screens

VCC-X Cnfg ID #

12 Rly Bd Relay (1-12)

Not Used

USE < or > TO CHANGE

The E-BUS 12 Relay Expansion Board Relays #1-#12 are confi gu-
rable for the following options (See Table 5, page 38 for Relay
descriptions):

Not Used (Default)

Cool

Stage

Heat

Stage

Mod Heat Enable

Mod Cool Enable

Warmup / Cooldown

ReHeat

PreHeat

Low

Ambient

Exhaust Fan

Economizer

Heat Wheel

Occupied

Mode

Override Mode

Alarm Active

Relays #1 through #12 can be individually confi gured. Only forms
of Heating and Cooling can be confi gured with multiple relays for
staging. If any other option is selected more than once, it will sim-
ply activate redundant relays, but no multiple staging will occur.
Default is Not Used.