Vcc-x configuration, Vcc-x confi guration screens – Orion System VCC-X Controller User Manual
Page 37

VCC-X Operator Interface SD
VCC-X CONFIGURATION
37
VCC-X Confi guration Screens
Confi guration Screens #70-76 - VCC-X Relay
Confi guration Screens
VCC-X Cnfg ID #
On-Board Relay (2-8)
Not Used
USE < or > TO CHANGE
Relay #1 is not confi gurable as it is reserved for the Supply Air Fan.
Relays #2-#8 are confi gurable for the following options (See Table
5, page 38 for Relay descriptions):
•
Not Used (Default)
•
Cool Stage
•
Heat
Stage
•
Mod Heat Enable
•
Mod Cool Enable
•
Warmup / Cooldown
•
ReHeat
•
PreHeat
•
Low
Ambient
•
Exhaust Fan
•
Economizer
•
Heat Wheel
•
Occupied
Mode
•
Override Mode
•
Alarm
Active
Relays #2 through #8 can be individually confi gured. Only forms
of Heating and Cooling can be confi gured with multiple relays for
staging. If any other option is selected more than once, it will sim-
ply activate redundant relays, but no multiple staging will occur.
Default is Not Used.
Confi guration Screens #77-81 - EM1 Relay
Confi guration Screens
VCC-X Cnfg ID #
EM1 Relay (1-5)
Not Used
USE < or > TO CHANGE
EM1 Relays #1-#5 are confi gurable for the following options (See
Table 5, page 38 for Relay descriptions):
•
Not Used (Default)
•
Cool
Stage
•
Heat
Stage
•
Mod Heat Enable
•
Mod Cool Enable
•
Warmup / Cooldown
•
ReHeat
•
PreHeat
•
Low
Ambient
•
Exhaust Fan
•
Economizer
•
Heat Wheel
•
Occupied
Mode
•
Override Mode
•
Alarm
Active
Relays #1 through #5 can be individually confi gured. Only forms of
Heating and Cooling can be confi gured with multiple relays for
staging. If any other option is selected more than once, it will simply
activate redundant relays, but no multiple staging will occur. Default
is Not Used.
Confi guration Screens #82-93 - E-BUS
12 Relay Confi guration Screens
VCC-X Cnfg ID #
12 Rly Bd Relay (1-12)
Not Used
USE < or > TO CHANGE
The E-BUS 12 Relay Expansion Board Relays #1-#12 are confi gu-
rable for the following options (See Table 5, page 38 for Relay
descriptions):
•
Not Used (Default)
•
Cool
Stage
•
Heat
Stage
•
Mod Heat Enable
•
Mod Cool Enable
•
Warmup / Cooldown
•
ReHeat
•
PreHeat
•
Low
Ambient
•
Exhaust Fan
•
Economizer
•
Heat Wheel
•
Occupied
Mode
•
Override Mode
•
Alarm Active
Relays #1 through #12 can be individually confi gured. Only forms
of Heating and Cooling can be confi gured with multiple relays for
staging. If any other option is selected more than once, it will sim-
ply activate redundant relays, but no multiple staging will occur.
Default is Not Used.
- VCB-X Controller VCB-X VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X Modular System Manager SD Modular System Manager SD Quick Start VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller VAV II Controller v.1 CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2