VAV/ZONE CONFIGURATION

VCC-X Operator Interface SD

74

Setpoint Screen #8 - Damper Airfl ow Night Min

and Fan On Min

XX Box Spts IDXXXX

Damper/Airflow Spt

Night Min.: XXX %
Fan On Min.:

XXX %

The Night Min is the position the damper will move to when the
system is in Override Mode and this particular damper is not part
of the override group. This Night Min position only affects non-fan
powered boxes. The Fan On Min is the minimum damper or airfl ow
setting used to activate the parallel fan if installed. Pressure Inde-
pendent = CFM. Pressure Dependent = %.

Description

Minimum

Default

Maximum

Night Min

0% or

0 CFM

0% or

0 CFM

100% or

9999 CFM

Fan On Min

0% or

0 CFM

25% or

250 CFM

100% or

9999 CFM

Setpoint Screen #9 - Damper Airfl ow Reheat Min

XX Box Spts IDXXXX

Damper/Airflow Spt

Reheat Min.: XXX %

The Reheat Min is the damper or airfl ow setting used during the
Space Reheat Mode of operation.

Description

Minimum

Default

Maximum

Reheat Min

0% or

0 CFM

0% or

0 CFM

100% or

30000 CFM

Setpoint Screen #10 - Damper Airfl ow Fixed

Position

XX Box Spts IDXXXX

Damper/Airflow Spt

Fixed Pos: XXX %

Many times while troubleshooting a system, it is useful to have the
zone damper set to a specifi c damper position or airfl ow setting. This
setpoint can be used to determine where the damper/airfl ow will
remain when the VAV/Zone Controller receives a Force to Fixed
Position
command.

Description

Minimum

Default

Maximum

Fixed Pos

0% or

0 CFM

0% or

0 CFM

100% or

9999 CFM

Setpoint Screen #11 - SAT HVAC Mode

Deadband

XX Box Spts IDXXXX

SAT HVAC Mode

Deadband.: XXºF

If the supply air temperature is above the space temperature by this
amount, the VAV/Zone controller enters the Supply Air Heating
Mode. It will remain in the Supply Air Heating Mode until the supply
air drops to 2ºF above the space temperature. At that point the unit
enters the Supply Air Vent Mode and remains there until the supply
air drops this deadband below the space temperature. At that point
the VAV/Zone Controller enters the Supply Air Cooling Mode and
will remain there until the supply air temperature rises to 2ºF below
the space temperature.

Description

Minimum

Default

Maximum

SAT HVAC Mode

Deadband

0ºF

10ºF

20ºF

Setpoint Screen #12 - Zone Alarm Offsets

XX Box Spts IDXXXX

Zone Alarm Offsets

Hi Zone......: XXºF

Lo Zone......: XXºF

The VAV/Zone Controller can be setup to generate an alarm anytime
the box goes into the Occupied Mode and the Zone Temperature ex-
ceeds the user-defi ned alarm limits for a user-defi ned period of time.
A High Temperature Alarm Setpoint is created by adding the Hi Zone
Alarm
offset to the current Cooling Setpoint. The Low Temperature
Alarm Setpoint
is created by adding the Lo Zone Alarm offset to the
current Heating Setpoint. If the zone temperature exceeds either of
these limits for a period defi ned by the Alarm Delay setpoint, the
controller can generate an alarm callout if all the optional hardware
components required for this to occur are installed.

Description

Minimum

Default

Maximum

Hi Zone Alarm

+1ºF

+30ºF

+50ºF

Lo Zone Alarm

-1ºF

-30ºF

-50ºF