VCC-X Operator Interface SD
VCC-X CONFIGURATION
33
Confi guration Screen #43 - Type of Airfl ow
Station
VCC-X Cnfg ID #
Airflow
Station: Paragon
USE < or > TO CHANGE
S
elect the type of Airfl ow Monitoring Station you are using, if any.
Selections are Ebtron or Paragon. Default is Paragon.
Confi guration Screen #44 - Monitor Outdoor
Air Airfl ow
VCC-X Cnfg ID #
Monitor OA Airflow
NO
USE < or > TO CHANGE
Select
YES if you have an Airfl ow Monitoring station measuring the
CFM of the Outdoor Air airfl ow stream of this unit. Default is NO.
Confi guration Screen #45 - Control Outdoor
Air CFM
VCC-X Cnfg ID #
Control Outdoor Air
CFM: NO
USE < or > TO CHANGE
Select
YES if you have an Airfl ow Monitoring station and are
controlling the Outdoor Air Damper to an airfl ow (CFM) Setpoint.
Default is NO.
Confi guration Screen #46 - Outdoor Airfl ow
Duct Size
VCC-X Cnfg ID #
Outdoor Airflow Duct
Size: 0.00
[ In Square Feet ]
For the controller to properly calculate the Outdoor Air CFM, you
need to enter the area in square feet of the Outdoor Air duct/damper.
When measuring the Outdoor Air duct damper area, be sure to mea-
sure the inside dimensions of the damper. The duct size needs to be
accurate to two decimal places. The more accurate the measurements,
the more accurate the CFM reading will be. Default is 0.
Description
Minimum
Default
Maximum
Outdoor Air Airfl ow Duct Size
0
0
200.00
VCC-X Confi guration Screens
Confi guration Screen #47 - Monitor Supply Air
Airfl ow
VCC-X Cnfg ID #
Monitor SA Airflow
NO
USE < or > TO CHANGE
Select
YES if you have an Airfl ow Monitoring station measuring the
CFM of the Supply Air airfl ow stream of this unit. Default is NO.
Confi guration Screen #48 - Supply Airfl ow
Duct Size
VCC-X Cnfg ID #
Supply Airflow Duct
Size: 0.00
[ In Square Feet ]
For the controller to properly calculate the Supply Air CFM, you need
to enter the area in square feet of the Supply Air duct/damper. When
measuring the Supply Air duct damper area, be sure to measure the
inside dimensions of the damper. The duct size needs to be accurate
to two decimal places. The more accurate the measurements, the
more accurate the CFM reading will be. Default is 0.
Description
Minimum
Default
Maximum
Supply Air Airfl ow Duct Size
0
0
200.00
Confi guration Screen #49 - Monitor Return Air
Airfl ow
VCC-X Cnfg ID #
Monitor RA Airflow
NO
USE < or > TO CHANGE
Select
YES if you have an Airfl ow Monitoring station measuring the
CFM of the Return Air airfl ow stream of this unit. Default is NO.
- VCB-X Controller VCB-X VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X Modular System Manager SD Modular System Manager SD Quick Start VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller VAV II Controller v.1 CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2