VCC-X CONFIGURATION

33

Confi guration Screen #43 - Type of Airfl ow

Station

VCC-X Cnfg ID #

Airflow

Station: Paragon

USE < or > TO CHANGE

S

elect the type of Airfl ow Monitoring Station you are using, if any.

Selections are Ebtron or Paragon. Default is Paragon.

Confi guration Screen #44 - Monitor Outdoor

Air Airfl ow

VCC-X Cnfg ID #

Monitor OA Airflow

NO

USE < or > TO CHANGE

Select

YES if you have an Airfl ow Monitoring station measuring the

CFM of the Outdoor Air airfl ow stream of this unit. Default is NO.

Confi guration Screen #45 - Control Outdoor

Air CFM

VCC-X Cnfg ID #
Control Outdoor Air

CFM: NO

USE < or > TO CHANGE

Select

YES if you have an Airfl ow Monitoring station and are

controlling the Outdoor Air Damper to an airfl ow (CFM) Setpoint.
Default is NO.

Confi guration Screen #46 - Outdoor Airfl ow

Duct Size

VCC-X Cnfg ID #

Outdoor Airflow Duct

Size: 0.00

[ In Square Feet ]

For the controller to properly calculate the Outdoor Air CFM, you
need to enter the area in square feet of the Outdoor Air duct/damper.
When measuring the Outdoor Air duct damper area, be sure to mea-
sure the inside dimensions of the damper. The duct size needs to be
accurate to two decimal places. The more accurate the measurements,
the more accurate the CFM reading will be. Default is 0.

Description

Minimum

Default

Maximum

Outdoor Air Airfl ow Duct Size

0

0

200.00

VCC-X Confi guration Screens

Confi guration Screen #47 - Monitor Supply Air

Airfl ow

VCC-X Cnfg ID #

Monitor SA Airflow

NO

USE < or > TO CHANGE

Select

YES if you have an Airfl ow Monitoring station measuring the

CFM of the Supply Air airfl ow stream of this unit. Default is NO.

Confi guration Screen #48 - Supply Airfl ow

Duct Size

VCC-X Cnfg ID #

Supply Airflow Duct

Size: 0.00

[ In Square Feet ]

For the controller to properly calculate the Supply Air CFM, you need
to enter the area in square feet of the Supply Air duct/damper. When
measuring the Supply Air duct damper area, be sure to measure the
inside dimensions of the damper. The duct size needs to be accurate
to two decimal places. The more accurate the measurements, the
more accurate the CFM reading will be. Default is 0.

Description

Minimum

Default

Maximum

Supply Air Airfl ow Duct Size

0

0

200.00

Confi guration Screen #49 - Monitor Return Air

Airfl ow

VCC-X Cnfg ID #

Monitor RA Airflow

NO

USE < or > TO CHANGE

Select

YES if you have an Airfl ow Monitoring station measuring the

CFM of the Return Air airfl ow stream of this unit. Default is NO.