VCC-X CONFIGURATION

35

Confi guration Screen #55 - Daylight Savings

Adjustment

VCC-X Cnfg ID #

Daylight Adjustment

Start Date: 0
Stop Date: 0

If you are in a time zone that does not have daylight savings time or
do not want to use this feature, leave these fi elds blank. Otherwise,
enter the starting date for Daylight Savings time in the Start Date
fi eld and the ending date in the Stop Date fi eld. For example, March
11 = 311 (DDMM). Default is 0000.

Description

Minimum

Default

Maximum

Start Date

0

0

1231

Stop Date

0

0

1231

NOTE:

The U.S. government has the authority to determine

the switch-over dates each year. Currently, the time
changes the second Sunday in March and then
switches back the fi rst Sunday in November.

Confi guration Screen #56 - Trend Log Rate

VCC-X Cnfg ID #

Trend Log

Rate: 15Min

[ 1 - 120 Minutes ]

An internal Trend Log is constantly updated at a rate equal to this
value. Trend Logs can only be accessed with Prism 2 software.
Default is 15 minutes.

Confi guration Screen #57 - Emergency

Shutdown

VCC-X Cnfg ID #

Emergency Shutdown

NO

USE < or > TO CHANGE

Select

YES if a Smoke Detector/Firestat or other Emergency Shut-

down input is connected to the Emergency Shutdown binary input.
If a Shutdown condition occurs and the 24V signal is removed from
this input, the Supply Fan and Heating and Cooling Relay Outputs
will be de-energized and an alarm will be generated. Default is NO.

Confi guration Screen #58 - Dirty Filter

VCC-X Cnfg ID #

Dirty Filter

NO

USE < or > TO CHANGE

Select

YES if a Dirty Filter switch is connected to the Dirty Filter

binary input. If the Dirty Filter input is active, an alarm will be
generated. Default is NO.

Confi guration Screen #59 - Broadcast OA Temp

VCC-X Cnfg ID #

Broadcast OA Temp

NO

USE < or > TO CHANGE

The VCC-X can broadcast its Outdoor Air Temperature Reading to
other HVAC units if they are not equipped with their own Outdoor Air
Temperature sensors. A network communications device (MiniLink
PD or CommLink) is needed in order for this feature to operate. Select
YES for Broadcast Outdoor Temperature. Default is NO.

Confi guration Screen #60 - Broadcast OA RH

VCC-X Cnfg ID #

Broadcast OA RH

NO

USE < or > TO CHANGE

The VCC-X can broadcast its Outdoor Air Humidity Reading to
other HVAC units if they are not equipped with their own Outdoor
Air RH sensors. A network communications device (MiniLink PD
or CommLink) is needed in order for this feature to operate. Select
YES for Broadcast Outdoor RH. Default is NO.

Confi guration Screen #61 - Broadcast Building

Pressure

VCC-X Cnfg ID #

Broadcast Build. Pr.

NO

USE < or > TO CHANGE

The VCC-X can broadcast Building Pressure from this unit to any
other unit requiring this value. Select YES for Broadcast Building
Pressure. Default is NO.