Vcc-x setpoints, Vcc-x setpoint screens, Vcc-x operator interface sd 40 – Orion System VCC-X Controller User Manual
Page 40: Setpoints - general procedures

VCC-X SETPOINTS
VCC-X Operator Interface SD
40
VCC-X Setpoint Screens
Setpoints - General Procedures
Modular Service Tool Instructions
From any menu screen, press
. The Unit Selection
Screen, shown below,
will appear requesting that you enter the unit
ID number.
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
Enter
the correct unit ID number of the VCC-X Controller you want
to change Setpoints for and press
. Once communication
is established, the *00* message will go away. Then
press
<
>
. You
will then see Setpoint Screen #1. Press
to save entered
data and
press
<
>
to scroll through the screens.
NOTE:
If the *00* remains, it indicates a communication
failure to the controller.
System Manager SD Instructions
From any Main screen, press
. The screen below
will appear because this option requires passcode clearance. Only
a Level 2 passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will
be displayed.
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
Enter the Unit ID of the controller you wish to change setpoints for
and press
. Once communication is established, the *00*
message will go away. Then
press
<
>
.
NOTE:
If the *00* remains, it indicates a communication
failure to the controller.
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
Scroll to the ‘Change Setpoints’ option and press
. This
will take you to the fi rst Setpoints Screen shown below.
Setpoint Screen #1 - Occupied HVAC Cool/
Heat Setpoints
VCC-X Spts ID:#
Occupied HVAC Spts
Cooling: 75.0ºF
Heating: 70.0ºF
These Setpoints are used to determine the Heating, Cooling, or
Vent Mode of operation in CAV applications using the Space or
Return Air Temperature Sensor as the Mode Enable Sensor (HVAC
Source) or in Make Up Air (MUA) applications using the Outdoor
Air Temperature Sensor as the Mode Enable Sensor (HVAC Source).
Description
Minimum
Default
Maximum
HVAC Mode
Setpoints Cooling
1ºF
(-17.2ºC)
75ºF
(24ºC)
110ºF
(43.3ºC)
HVAC Mode
Setpoints Heating
1ºF
(-17.2ºC)
70ºF
(21ºC)
110ºF
(43.3ºC)
Setpoint Screen #2 - Hood On HVAC Setpoints
- OAT Cool, OAT Heat
VCC-X Spts ID:#
Hood On HVAC Spts
OAT Cool: 75.0ºF
OAT Heat: 70.0ºF
These setpoints are used for two different applications.
CAV/MUA Dual Mode (Hood On/Off)—In CAV (Hood Off) opera-
tion, the unit will use the Occupied HVAC Setpoints from Setpoint
Screen #1 in reference to a Space or Return Air Temperature Sensor.
When exhaust hoods are turned on and the Hood On contact closes,
the unit switches from CAV Space Temperature Control to MUA
Outdoor Air Temperature control operation (Hood On). At this point
the Outdoor Damper modulates to full open, and these Hood On set-
points become the Outdoor Air Temperature Mode Enable Setpoints.
- VCB-X Controller VCB-X VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X Modular System Manager SD Modular System Manager SD Quick Start VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller VAV II Controller v.1 CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2