Vcc-x setpoints, Vcc-x setpoint screens, Vcc-x operator interface sd 40 – Orion System VCC-X Controller User Manual

Page 40: Setpoints - general procedures

background image

VCC-X SETPOINTS

VCC-X Operator Interface SD

40

VCC-X Setpoint Screens

Setpoints - General Procedures

Modular Service Tool Instructions

From any menu screen, press

. The Unit Selection

Screen, shown below,

will appear requesting that you enter the unit

ID number.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter

the correct unit ID number of the VCC-X Controller you want

to change Setpoints for and press

. Once communication

is established, the *00* message will go away. Then

press

<

>

. You

will then see Setpoint Screen #1. Press

to save entered

data and

press

<

>

to scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

System Manager SD Instructions

From any Main screen, press

. The screen below

will appear because this option requires passcode clearance. Only
a Level 2 passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will
be displayed.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter the Unit ID of the controller you wish to change setpoints for
and press

. Once communication is established, the *00*

message will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

The following screen will be displayed:

Change Setpoints
Configure Unit
Save/Copy/Restore

Scroll to the ‘Change Setpoints’ option and press

. This

will take you to the fi rst Setpoints Screen shown below.

Setpoint Screen #1 - Occupied HVAC Cool/

Heat Setpoints

VCC-X Spts ID:#

Occupied HVAC Spts

Cooling: 75.0ºF
Heating: 70.0ºF

These Setpoints are used to determine the Heating, Cooling, or
Vent Mode of operation in CAV applications using the Space or
Return Air Temperature Sensor as the Mode Enable Sensor (HVAC
Source) or in Make Up Air (MUA) applications using the Outdoor
Air Temperature Sensor as the Mode Enable Sensor (HVAC Source).

Description

Minimum

Default

Maximum

HVAC Mode
Setpoints Cooling

1ºF

(-17.2ºC)

75ºF

(24ºC)

110ºF

(43.3ºC)

HVAC Mode
Setpoints Heating

1ºF

(-17.2ºC)

70ºF

(21ºC)

110ºF

(43.3ºC)

Setpoint Screen #2 - Hood On HVAC Setpoints

- OAT Cool, OAT Heat

VCC-X Spts ID:#

Hood On HVAC Spts

OAT Cool: 75.0ºF
OAT Heat: 70.0ºF

These setpoints are used for two different applications.

CAV/MUA Dual Mode (Hood On/Off)—In CAV (Hood Off) opera-
tion, the unit will use the Occupied HVAC Setpoints from Setpoint
Screen #1 in reference to a Space or Return Air Temperature Sensor.
When exhaust hoods are turned on and the Hood On contact closes,
the unit switches from CAV Space Temperature Control to MUA
Outdoor Air Temperature control operation (Hood On). At this point
the Outdoor Damper modulates to full open, and these Hood On set-
points become the Outdoor Air Temperature Mode Enable Setpoints.