VCC-X SETPOINTS

49

Reverse Acting Building Pressure Control

Outdoor Air Damper—

If this option is confi gured,

the VCC-X will use the user-adjustable Economizer/

Outdoor Air Damper output signal (AOUT2 –

Economizer Control Signal) to maintain the Building

Pressure Setpoint. Whenever the Building Pressure

falls below the Building Pressure Setpoint by the

Deadband amount, the modulating Economizer Output

Signal will modulate the damper open to control to

the Building Pressure Setpoint. If the Building Pressure

rises above the Building Pressure Setpoint by the

Deadband amount, the damper will modulate towards

closed as it attempts to maintain the Building Pressure

Setpoint. When this option is selected, no Economizer

free cooling or CO

2

IAQ operation will be available.

Supply Fan VFD

– Contact WattMaster regarding this

Reverse Acting Building Pressure Control option. It

should not be used in most applications. If this option

is selected, the user-adjustable Supply Fan VFD Output

(AOUT1 on the VCC-X) will be used to control the

Supply Fan VFD to maintain the Building Pressure

Setpoint in similar fashion to the Outdoor Air Damper

control described above.

Description

Min.

Default

Max.

Building Pressure Spt

-0.20″ WG

0.02″ WG

0.20″ WG

Building Pressure
Deadband

0.01″ WG

0.01″ WG

0.10″ WG

Setpoint Screen #31 - OAT Lockouts -

Comp Cool/Comp Heat

VCC-X Spts ID:#

OAT Lockouts

Comp Cool: 50.0ºF
Comp Heat: 35.0ºF

The VCC-X will Lockout Compressor (Mechanical) Cooling and
Heat Pump Compressor Heating when the Outdoor Air Temperature
is below these Compressor Cool and Heat Lockout Setpoints.

Description

Minimum

Default

Maximum

OAT Lockout
Compressor Cooling

-30ºF

(-34.4

º

C)

50ºF

(10

º

C)

100ºF

(37.7

º

C)

OAT Lockout
Compressor Heating

-30ºF

(-34.4

º

C)

35ºF

(1.6

º

C)

100ºF

(37.7

º

C)

Setpoint Screen #32 - OAT Lockouts - Heat

VCC-X Spts ID:#

OAT Lockouts

Heat: 90.0ºF

The VCC-X will Lockout Mechanical Heating when the Outdoor
Air Temperature is above this Setpoint.

Description

Minimum

Default

Maximum

OAT Lockouts Heating

-30ºF

(34.4

º

C)

90ºF

(32.2

º

C)

150ºF

(65.5

º

C)

Setpoint Screen #33 - Supply Air Cutoffs -

Cooling/Heating

VCC-X Spts ID:#

Supply Air Cutoffs

Cooling: 40.0ºF
Heating: 150.0ºF

The VCC-X controller will temporarily disable Heating or Cooling
if while in Heating or Cooling Mode the Supply Air Temperature
rises above the Hi SAT Cutoff Heating Setpoint or falls below the
Lo SAT Cutoff Cooling Setpoint. See the VCC-X Controller Techni-
cal Guide
for detailed information on the Low and High Supply Air
Temperature Cutoff sequence of operation.

Description

Minimum

Default

Maximum

Cooling SAT Cutoff

0ºF

(-17.7

º

C)

40ºF

(4.5

º

C)

100ºF

(37.7

º

C)

Heating SAT Cutoff

0ºF

(-17.7

º

C)

150ºF

(65.5

º

C)

250ºF

(121.1

º

C)

Setpoint Screen #34 - Mod Heat Output

Position in Off Mode

VCC-X Spts ID:#

Mod Heat Output Pos

In Off Mode: 0%

This screen can be used to ensure that a Modulating Hot Water
Valve will open to a certain position when the fan is not operating
in order to prevent freezing. For other forms of Modulating Heat,
this would normally be set to 0%.

Description

Minimum

Default

Maximum

Mod Heat Output
Position in Off Mode

0%

0%

100%