VCC-X Operator Interface SD

MINILINK PD CONFIGURATION

79

MiniLink PD Confi guration Screens

MiniLink PD Confi guration

NOTE:

If this is not a voting system, the only screens you

need to confi gure are Screens 6 through 65 if alarm
polling pertains to your system.

In order to correctly setup the MiniLink PD, you must fi rst confi gure
several parameters in regard to the type of system and operating
parameters for the system it is installed on. Most of these values
and operating parameters are only set once at the initial system setup
and are never changed.

Modular Service Tool Instructions

From any menu screen, press

. The Unit Selection

Screen, shown below,

will appear requesting that you enter the unit

ID number.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

All MiniLink PDs are set at address 60. Enter the correct unit loop

number for the loop the MiniLink Polling Device is connected to
(for Loop 1 you would enter

<160>

) and press

. Once

communication is established, the *00* message will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

You will then see Setpoint Screen #1. Press

to save en-

tered data and

press

<

>

to scroll through the screens.

System Manager SD Instructions

From any Main screen, press

. The screen below

will appear because this option requires passcode clearance. Only a
Level 2 passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will
be displayed.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter the Unit ID of the controller you wish to change schedules for
and press

. Once communication is established, the *00*

message will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

The following screen will be displayed:

Change Setpoints

Configure Unit

Save/Copy/Restore

Scroll to the ‘Change Setpoints’ option and press

. This

will take you to the fi rst Setpoints Screen shown below.

Confi guration Screen #1 - System Type

Polling Unit Config

System Type

Selection: ZONING

Use < Or > To Change

This screen allows you to select whether you want the system to
behave as a VAV system or a Zoning System. If you select VAV, this
will allow tenant logging for your VAV system.

Confi guration Screen #2 - Last Polled Zone

Polling Unit Config

Last Polled Zone

Address: XX

[Enter Last Zone]

This zone is the last zone on the local loop of your zoning system
that is to be included in zone voting.

Confi guration Screen #3 - Mode Changeover

Time

Polling Unit Config

Mode Changeover Time

Minutes: XX

[Enter Period Time]

This is the amount of time that you want to allow between changeover
from heating to cooling modes.