Vcc-x configuration, Vcc-x confi guration screens, Vcc-x operator interface sd 28 – Orion System VCC-X Controller User Manual

Page 28

background image

Zone

Zone

VCC-X CONFIGURATION

VCC-X Operator Interface SD

28

VCC-X Confi guration Screens

Confi guration Screen #15 - Return Sensor

Type

VCC-X Cnfg ID #

Return Sensor Type

NONE

USE < or > TO CHANGE

If this unit has a Return Air Sensor installed, select Analog if it is a
wired Thermistor temperature sensor. Select E-bus Return/RH if it
is a combination communicating temperature and humidity sensor.
Default is NONE.

Confi guration Screen #16 - Static Pressure

Control

VCC-X Cnfg ID #

Static Pr Control

Fan VFD

USE < or > TO CHANGE

Select what type of Duct Static Pressure is being controlled, if any.
Default is Fan VFD. The options are:

None

— This unit is not controlling Duct Static Pressure.

Fan VFD

—This unit has a Supply Fan VFD that

modulates to control the Duct Static Pressure or this is a

Single Zone VAV application.

Bypass Damper

This unit uses a Bypass Damper to

control the Duct Static Pressure.

Confi guration Screen #17 - Static/Fan Control

Rate

VCC-X Cnfg ID #

Static/Fan Control

Rate: 10s

[ 1 - 30 Seconds ]

This value determines the time interval between changes to the Sup-
ply Fan Speed or the Bypass Damper Position during Duct Static
Pressure Control. It also determines the time interval between
changes to the Fan Speed during Single Zone VAV Reset of the
Supply Fan VFD Speed. Default is 10 seconds.

Confi guration Screen #18 - Static Pressure

Control Rate Max Adjust

VCC-X Cnfg ID #

Static Pr. Control

Max Adjust: 5%

[ 1 - 30% ]

This is the maximum amount that the Static Pressure Control output
can adjust to when it needs to. Default is 5 percent.

Confi guration Screen #19 - Fan Voltage

Output

VCC-X Cnfg ID #

Fan Voltage Output

Min Volts: 0.0VDC

Max Volts: 10.0VDC

Enter

a value between 0.0 and 10.0 VDC for the main fan’s minimum

and maximum output voltage. The Duct Static Pressure Output
Status Screen
will display 0% to 100%, but the output will range
from the minimum value set on this screen to the maximum value
set on this screen.

The VCC-X will reverse the logic of the output signal when a Zoning
Bypass Damper is used. Defaults are 0 VDC Min and 10 VDC Max.

Description

Minimum

Default

Maximum

Minimum Fan Voltage

0

0

10

Maximum Fan Voltage

0

10

10

Confi guration Screen #20 - Fan Cycle Mode

VCC-X Cnfg ID #

Fan Cycle Mode

NO

USE < or > TO CHANGE

Select

YES if you want the HVAC unit’s Supply Fan to only run dur-

ing Heating or Cooling Mode. If you want the HVAC unit’s Supply
Fan to run continuously while in the Occupied Mode, regardless of
the Heating or Cooling Mode, select NO. Default is NO.

Confi guration Screen #21 - Fan Proving

VCC-X Cnfg ID #

Fan Proving

NO

USE < or > TO CHANGE

Select

YES if the unit is equipped with a Proof of Flow Switch and

it is connected to the VCC-X. If selected as YES and the Proof of
Flow Switch is open, only the Supply Fan Relay will be active. If
any other relays such as Heating Stages or Cooling Stages are ac-
tive, they will be deactivated when the Proof of Flow Switch input
is lost. Default is NO.