Vcc-x configuration, Vcc-x confi guration screens, Vcc-x operator interface sd 28 – Orion System VCC-X Controller User Manual
Page 28

Zone
Zone
VCC-X CONFIGURATION
VCC-X Operator Interface SD
28
VCC-X Confi guration Screens
Confi guration Screen #15 - Return Sensor
Type
VCC-X Cnfg ID #
Return Sensor Type
NONE
USE < or > TO CHANGE
If this unit has a Return Air Sensor installed, select Analog if it is a
wired Thermistor temperature sensor. Select E-bus Return/RH if it
is a combination communicating temperature and humidity sensor.
Default is NONE.
Confi guration Screen #16 - Static Pressure
Control
VCC-X Cnfg ID #
Static Pr Control
Fan VFD
USE < or > TO CHANGE
Select what type of Duct Static Pressure is being controlled, if any.
Default is Fan VFD. The options are:
None
— This unit is not controlling Duct Static Pressure.
Fan VFD
—This unit has a Supply Fan VFD that
modulates to control the Duct Static Pressure or this is a
Single Zone VAV application.
Bypass Damper
—This unit uses a Bypass Damper to
control the Duct Static Pressure.
Confi guration Screen #17 - Static/Fan Control
Rate
VCC-X Cnfg ID #
Static/Fan Control
Rate: 10s
[ 1 - 30 Seconds ]
This value determines the time interval between changes to the Sup-
ply Fan Speed or the Bypass Damper Position during Duct Static
Pressure Control. It also determines the time interval between
changes to the Fan Speed during Single Zone VAV Reset of the
Supply Fan VFD Speed. Default is 10 seconds.
Confi guration Screen #18 - Static Pressure
Control Rate Max Adjust
VCC-X Cnfg ID #
Static Pr. Control
Max Adjust: 5%
[ 1 - 30% ]
This is the maximum amount that the Static Pressure Control output
can adjust to when it needs to. Default is 5 percent.
Confi guration Screen #19 - Fan Voltage
Output
VCC-X Cnfg ID #
Fan Voltage Output
Min Volts: 0.0VDC
Max Volts: 10.0VDC
Enter
a value between 0.0 and 10.0 VDC for the main fan’s minimum
and maximum output voltage. The Duct Static Pressure Output
Status Screen will display 0% to 100%, but the output will range
from the minimum value set on this screen to the maximum value
set on this screen.
The VCC-X will reverse the logic of the output signal when a Zoning
Bypass Damper is used. Defaults are 0 VDC Min and 10 VDC Max.
Description
Minimum
Default
Maximum
Minimum Fan Voltage
0
0
10
Maximum Fan Voltage
0
10
10
Confi guration Screen #20 - Fan Cycle Mode
VCC-X Cnfg ID #
Fan Cycle Mode
NO
USE < or > TO CHANGE
Select
YES if you want the HVAC unit’s Supply Fan to only run dur-
ing Heating or Cooling Mode. If you want the HVAC unit’s Supply
Fan to run continuously while in the Occupied Mode, regardless of
the Heating or Cooling Mode, select NO. Default is NO.
Confi guration Screen #21 - Fan Proving
VCC-X Cnfg ID #
Fan Proving
NO
USE < or > TO CHANGE
Select
YES if the unit is equipped with a Proof of Flow Switch and
it is connected to the VCC-X. If selected as YES and the Proof of
Flow Switch is open, only the Supply Fan Relay will be active. If
any other relays such as Heating Stages or Cooling Stages are ac-
tive, they will be deactivated when the Proof of Flow Switch input
is lost. Default is NO.
- VCB-X Controller VCB-X VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X Modular System Manager SD Modular System Manager SD Quick Start VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller VAV II Controller v.1 CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2