Network Mode & Multiple Managers
Loop Search
When the System Manager is confi gured for Network Mode, a loop
search must initially be performed for the System Manager to rec-
ognize alarms or overrides. Also, when you have a system that has
multiple System Managers and you have one of the System Managers
set to (63) Network Mode for alarm and override indication, you must
also perform a loop search for that System Manager. This allows
the System Manager to be aware of all alarms and overrides for all
local loops on the entire system.
To access the Loop Search Screen, from the Setup Screen, press
and then press
.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Press
<
>
for Next Menu. The following screen will be displayed:
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
Press
<4>
for Loop Search. The following screen will be displayed:
Loop Search
Current Loop = XX
Loops Found = XX
Searching
The System Manager will now proceed to search all loops to fi nd
the MiniLink PDs that are connected to the system. The screen will
display the current loop being searched and the number of loops
currently found.
Once the search is completed, the following screen will be displayed:
Loop Search
Finished
Loops Found = XX
Press ESC to Exit
The screen will display the number of loops found on your system.
The information will be saved into the System Manager’s memory.
No further loop searches will be required unless you add an additional
MiniLink PD to the Network System.
Loop Search and System Alarm Search
System Alarm Search
The System Manager can be used to search for all active alarms
on the system. You must confi gure the MiniLink PD to allow for
“ Alarm Polling” for each controller you want polled for alarms. See
the MiniLink PD programming section on page 79 of this manual
for setting information.
This option will alert you of the number of alarms present on indi-
vidual units, but will not tell you what type of alarm are present. You
will have to perform and individual unit alarm search for detailed
alarm information.
To access the Alarm Search Screen, from the Setup Screen, press
and then press
.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Press
<
>
for Next Menu. The following screen will be displayed:
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
Press
<
>
for Next Menu. The following screen will be displayed:
5) Alarm Search
NEXT) More Options
ESC) Exit Menu
Press
<5>
for Alarm Search. The entire system is searched from this
point. The following screen will be displayed:
Alarm Screen
SEARCHING!
Once the Alarm Search is complete, one of the following screens
will display:
Alarm Screen
XX ALARMS ON UNIT XX
- VCB-X Controller VCB-X VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X Modular System Manager SD Modular System Manager SD Quick Start VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller VAV II Controller v.1 CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2