VCC-X CONFIGURATION

VCC-X Operator Interface SD

26

VCC-X Confi guration Screens

Confi guration Screen #3 - RSM #3 & #4

Modules Installed

VCC-X Cnfg ID #
RSM#3 Installed: NO
RSM#4 Installed: NO

USE < or > TO CHANGE

If you have a 3rd RSMV Module installed, the 1st confi guration op-
tion should be confi gured as YES. If you have a 4th RSMV Module
installed, the 2nd confi guration option should be confi gured as YES.
Default is NO.

Confi guration Screen #4 - EM1 Expansion

Module Installed

VCC-X Cnfg ID #

EM1 Installed: NO

USE < or > TO CHANGE

If you have Expansion Module EM1 installed, this confi guration
option should be confi gured as YES. Default is NO. If your unit
utilizes the following, an EM1 Module is required:

Modulating Chilled Water

 

Return Air Bypass Control

 

Title 24 Economizer Actuator Feedback

Confi guration Screen #5 - MHGRV-X &

MODGAS-X Installed

VCC-X Cnfg ID #
MHGRV Installed: NO
MODGS Installed: NO

USE < or > TO CHANGE

If you have an MHGRV-X Controller installed, the fi rst confi gura-
tion option should be confi gured as YES. If you have a MODGAS-
X Controller installed, the second confi guration option should be
confi gured as YES. Defaults are NO.

Confi guration Screen #6 - 12 Relay E-BUS

Expansion Module Installed

VCC-X Cnfg ID #

12RLY Installed: NO

USE < or > TO CHANGE

If you have a 12 Relay E-BUS Expansion Module installed, this
confi guration option should be confi gured as YES. Default is NO.

Confi guration Screen #7 - PREHEAT-X

Controller Installed

VCC-X Cnfg ID #

Preheat-X

Installed: NO

USE < or > TO CHANGE

If you have a PREHEAT-X Controller installed, this confi guration
option should be confi gured as YES. Default is NO.

Confi guration Screen #8 - HVAC Mode Enable Source

VCC-X Cnfg ID #

HVAC Source

Supply Air

USE < or > TO CHANGE

This selects which sensor will determine the mode of operation of
the unit and how it will operate. Default is Supply Air. Available
options are:

 

Supply Air

—This is for a standard Cooling Only VAV

unit with optional Morning Warm Up. In the Occupied

Mode, the unit will be in the Cooling Mode controlling

to the Cooling Supply Air Setpoint.

Supply Air/Tempering

—This selection is for VAV

“cooling only” applications where because of cold

outdoor temperatures, heat may need to be added in

order to maintain the “Cooling” Supply Air Setpoint.

This application requires Outdoor Air Enable Setpoints

to be confi gured in order to initiate Cooling and Heating

Modes. The Cooling and Heating Supply Air Setpoints

can then both be set to the same temperature (e.g. 55

º

).

Outdoor Air

—This is for a 100% OA Unit (MUA) using

the OA Temperature Sensor to determine the Heating,

Cooling, and Vent Modes of operation. Dehumidifi cation

utilizes an Outdoor Air Dewpoint Setpoint.

Return Air

—Optional recirculating unit confi guration

using the Return Temperature Sensor to determine the

Heating, Cooling, and Vent Modes of operation.

Space Temperature

—Typical recirculating unit using

a Space Temperature Sensor to determine the Heating,

Cooling, and Vent Modes of operation.

Space Temperature with High % OA CFM—

If it is

preferable to use Space conditions (instead of Outside

Air) to control a 100% or high percentage outdoor air

unit, this option allows tempering of the outdoor air in

the Space Vent Mode of operation to prevent dumping of

hot or cold air into the space. See the Sequence of

Operations for details.

Single Zone VAV

—Recirculating unit using the Space

Temperature Sensor to determine the mode of operation.

Heating and Cooling are controlled to a Leaving Air

Setpoint. Space Temperature resets the Supply Fan VFD

speed to maintain the Space Temperature. Modulating

Heating and Cooling must be used for this operation.

Can be confi gured for CAV Heating using staged Heat.