Confi guration Screen #22 - Fan Starting Delay

VCC-X Cnfg ID #

Fan Starting

Delay: -1s

[-1 = Unit Addr x 5]

Enter the number of seconds you want the fan to delay starting. This is
the Supply Fan Starting Delay initiated whenever the VCC-X initiates
Supply Fan operation upon going occupied or after power-up. This is
useful when you are using multiple VCC-X-controlled HVAC units and
want to be sure that all the units do not start at exactly the same time
when the Occupied schedule occurs. Each VCC-X should be set with
staggered Fan Starting Delay Setpoint values. When the -1 value is used,
it multiplies each VCC-X Controller’s address by 5 and uses this value
in seconds as the Fan Starting Delay. This provides a staggered start for
each VCC-X Controller on the system without having to individually set
each VCC-X Controller for its own time delay.

For an MUA unit, this

should be set to a minimum of 60 seconds to let the OA Damper
open. Default is -1 second.

Description

Minimum

Default

Maximum

Fan Start Delay Timer

-1 Sec

-1 Sec

240 Sec

Confi guration Screen #23 - Purge Mode Delay

VCC-X Cnfg ID #

Purge Mode
Delay: 10s

[ 0 - 900 Seconds ]

Enter the number of seconds you want the unit to stay in Purge Mode
before going into Occupied Mode. In Purge Mode, the fan runs with the
Economizer closed and all Cooling and Heating is de-energized.

For an

MUA unit, this should be set to 0 seconds to prevent a Purge Mode
(which is a damper closed operation). Default is 10 seconds.

Confi guration Screen #24 - Heat Type

VCC-X Cnfg ID #

Heat Type

No Heat

USE < or > TO CHANGE

Default is No Heat. Available options are:

No Heat

—The unit has no Heat.

Staged Only

—On/Off Hot Water or fi xed stage(s) of Heat.

Mod Heat Only

—Only fully modulating forms of

Heat which would be Modulating Hot Water or Steam Heat

or Modulating SCR Electric Heat. Does not include

Modulating Gas using the AAON

®

MODGAS-X

Controller.

VCC-X Confi guration Screens

Mod Heat Then Staged

—Fully modulating Heat as the

1

st

form of Heat and Stage(s) of Heat as the 2

nd

form of

Heat.

Mod Gas Heat Only

—Only Modulating Gas Heat

controlled by the AAON

®

MODGAS-X Controller.

Mod Gas Then Staged

—ModGas Heat as the 1

st

form

of Heat and Stage(s) of Heat as the 2

nd

form of Heat.

See the VCC-X Controller Technical Guide for a more detailed descrip-
tion of these operations.

Confi guration Screen #25 - Modulating Heat

Output Signal

VCC-X Cnfg ID #

Mod Heat Volt Output

Min Pos Volts: 0.0
Max Pos Volts: 10.0

Enter

a value between 0.0 and 10.0 VDC for the Modulating Heat

minimum and maximum output voltage. When performing reverse
acting heating, the minimum position volts will be the highest value.
Defaults are 0 VDC Min and 10 VDC Max.

Description

Minimum

Default

Maximum

Minimum Position Volts

0

0

10

Maximum Position Volts

0

10

10

Confi guration Screen #26 - Cool Type

VCC-X Cnfg ID #

Cool Type

Refrigeration Module

USE < or > TO CHANGE

Default is Refrigeration Module. Available options are:

Refrigeration Module

—A Refrigeration Module is

installed and confi gured.

Staged Only

—On/Off Chilled Water or fi xed stage(s)

DX Cooling only and no Compressor Dehumidifi cation.

Mod Only

— Modulating Chilled Water