VCC-X CONFIGURATION

VCC-X Operator Interface SD

32

Confi guration Screen #39 - Exhaust Fan

Output

VCC-X Cnfg ID #

Exh Fan Volts

Min Volts: 0.0VDC
Max Volts: 10.0

VDC

This confi guration option is available if Modulating Building Pres-
sure Control was confi gured on a previous screen. The following
will set the output voltage range for both Direct and Reverse Acting
Building Pressure Control. Defaults are 0 VDC Min Volts and 10
VDC Max Volts.
Available options are:



Min Volts

—Voltage at which the signal to exhaust fan,

exhaust damper, or OA damper will be at 0% for either

Direct or Reverse Acting Building Pressure control.



Max Volts

—Voltage at which the signal to exhaust fan,

exhaust damper, or OA damper will be at 100% for

either Direct or Reverse Acting Building Pressure

control.

Description

Minimum

Default

Maximum

Minimum Position Volts

0.0

0.0

10.0

Maximum Position Volts

0.0

10.0

10.0

Confi guration Screen #40 - Dehumidifi cation

Control

VCC-X Cnfg ID #

Dehum. Control:

None

USE < or > TO CHANGE

If using Dehumidifi cation choose the appropriate Dehumidifi cation
option. Default is None. Available options are:

None

—The unit does not have a Dehumidifi cation

Mode.

Only Occupied Vent

—The unit can only enter

Dehumidifi cation during the Occupied Vent Mode (when

there is no call for Cooling or Heating).

Only Vent Anytime

—The unit can only enter

Dehumidifi cation during the Vent Mode (when there

is no call for Cooling or Heating) in both the Occupied

and Unoccupied operation.

All Modes Occupied

—This is Occupied Mode

Dehumidifi cation Priority. The unit can enter
Dehumidifi cation during Cooling, Heating, or Vent

Modes, but only while in Occupied operation.

VCC-X Confi guration Screens

All Modes Anytime

—This is Occupied and

Unoccupied

Dehumidifi cation Priority. The unit can

enter

Dehumidifi cation during Cooling, Heating, or Vent

Modes while in Occupied or Unoccupied operation.

For units controlled by space humidity sensors, Dehumidifi cation
is initiated based on an Indoor Humidity Setpoint. For 100% OA
units (MUA), Occupied Dehumidifi cation is initiated based on
an Outdoor Air Dewpoint Setpoint. For MUA units, Unoccupied
Dehumidifi cation can only occur if the unit is confi gured for Night
Setback recirculating operation and has a Space Humidity sensor
and a Space Humidity Setpoint.

Confi guration Screen #41 - Humidity Control

Sensor Type

VCC-X Cnfg ID #

Humidity Control

Sensor: Space

USE < or > TO CHANGE

Select Space, Return, or Outdoor if an E-BUS Humidity Sensor is
installed. Default is Space.

Confi guration Screen #42 - Reheat Type

VCC-X Cnfg ID #

Reheat Control

None

USE < or > TO CHANGE

This confi guration option is available if Dehumidifi cation has been
confi gured. If you need Reheat in the Dehumidifi cation mode, this
screen allows you to confi gure what kind of reheat will be used.

The output(s) will be staged or modulated to maintain the Active
Supply Air Setpoint. Default is None. Select

the type of reheat that

will be used during dehumidifi cation.



None

—No reheat.



On/Off HGR Relay

—Single On/Off Reheat stage

(Reheat Relay).



Mod HGR

—Modulating Hot Gas Reheat (MHGR)



Unit Heat

—Using the unit’s heat as Reheat when Hot

Gas Reheat is not available.



Mod HGR + Unit Heat

—Using MHGR as the 1

st

form of Reheat, supplemented by unit Heat if necessary.



On/Off HGR + Unit Heat

—Using “Reheat Relay”

stage as the 1

st

form of Reheat, supplemented by unit

Heat if necessary.