VCC-X CONFIGURATION

VCC-X Operator Interface SD

34

VCC-X Confi guration Screens

Confi guration Screen #50 - Return Airfl ow

Duct Size

VCC-X Cnfg ID #

Return Airflow Duct

Size: 0.00

[ In Square Feet ]

For the controller to properly calculate the Return Air CFM, you need
to enter the area in square feet of the Return Air duct/damper. When
measuring the Return Air duct damper area, be sure to measure the
inside dimensions of the damper. The duct size needs to be accurate
to two decimal places. The more accurate the measurements, the
more accurate the CFM reading will be. Default is 0.

Description

Minimum

Default

Maximum

Return Air Airfl ow Duct
Size

0

0

200.00

Confi guration Screen #51 - Monitor Exhaust

Airfl ow

VCC-X Cnfg ID #
Monitor Exh Airflow

NO

USE < or > TO CHANGE

Select

YES if you have an Airfl ow Monitoring station measuring the

CFM of the Exhaust Air airfl ow stream of this unit. Default is NO.

Confi guration Screen #52 - Exhaust Airfl ow

Duct Size

VCC-X Cnfg ID #

Exhaust Airflow Duct

Size: 0.00

[ In Square Feet ]

For the controller to properly calculate the Exhaust Air CFM, you
need to enter the inside area in square feet of the Exhaust Air duct/
damper. When measuring the Exhaust Air damper area, be sure to
measure the inside dimensions of the damper. The duct size needs to
be accurate to two decimal places. The more accurate the measure-
ments, the more accurate the CFM reading will be. Default is 0.

Description

Minimum

Default

Maximum

Exhaust Airfl ow Duct Size

0

0

200.00

Confi guration Screen #53 - Morning Warm Up

VCC-X Cnfg ID #

Morning Warm Up

None

USE < or > TO CHANGE

You can choose between the following Morning Warm Up options.
Default is None. Available options are:

None

— There is no Morning Warm Up required.

Stand Alone

The VCC-X Controller is not

communicating to Orion VAV Box controls, but a

Morning Warm Up Relay can be confi gured to signal

boxes by others to open.

Bcast Fixed to Boxes

—The VCC-X Controller is

communicating to Orion VAV Boxes and will broadcast

a command to the boxes to go to a Fixed Percentage

Position

or

Airfl ow while in Morning Warm Up. This

fi xed position is confi gured in the VAV Box Controller.

Bcast Max to Boxes

—The VCC-X Controller is

communicating to Orion VAV Boxes and will broadcast

a command to the boxes to go to a Maximum Percentage

Position

or

Airfl ow while in Morning Warm Up. This

maximum position is confi gured in the VAV Box

Controller.

Confi guration Screen #54 - AHU Uses

Schedule Number

VCC-X Cnfg ID #

AHU Uses Schedule

Number: 0

[‘0’ For Internal]

The VCC-X has an internal schedule. If you want the VCC-X to use
its own internal schedule, enter

<0>

for Internal.

External Schedules are available by using one of the GPC-X family
of General Purpose Controllers. Depending on which generation of
GPC-X Controller you have, you may have up to 5 or up to 8 sched-
ules available to use. To use the schedules on one of these controllers,
enter the number of the schedule on that controller (either 1 through
5 or 1 through 8) you will be using. Default is 0.

Description

Minimum

Default

Maximum

AHU Uses Schedule

0

0

8