VCC-X Operator Interface SD

MODULAR SYSTEM MANAGER SD

21

Unit Alarm Search and Override Search

Alarm Screen

NO ALARMS DETECTED

To check controllers individually for alarms, use the

button on the Main Display.

Unit Alarm Search

The System Manager can be used to search for all active alarms one
controller at a time.

Press

. The Unit Selection Screen below will be displayed.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter the Unit ID of the controller you wish to search and press

. Once communication is established, the *00* message

will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

The following screen will appear. The System Manager will search
for any active alarms on the unit and one of the following screens
will appear:

CONTROLLER V.XXX

NO ALARMS

CONTROLLER V.XXX

ALARMS PRESENT

SCROLL DOWN TO VIEW

Press

<

>

to scroll through all the alarms for the controller that the

Modular Service Tool is connected to.

To clear any alarms that are found, you must fi x the problem indicated
in the alarm. Once the problem is fi xed, the alarm will clear from
the screen the next time the unit is polled.

System Manager Override Search

NOTE:

In order for the Override Search to work, a Loop

Search must be performed fi rst. See page 20 for de-
tails.

When a space sensor with override option is used with any VAV/Zone
Controller or Unit Controller, the System Manager can determine
and report any controllers that are currently operating in an override
condition. This function requires that a MiniLink PD is installed on
each loop where the controllers may be located. The MiniLink PD
must be confi gured to allow for “Alarm Polling” for each controller
that Override Polling Enabled is desired for this function to work. See
the MiniLink PD programming section on page 79 of this manual
for setting information.

To access the Space Sensor Overrides Screen, press

,

The following screen will appear.

Overrides Screen

SEARCHING!

After the System Manager completes its search, it will list the fi rst
unit on the system that is currently in the override mode. Press the

<

>

button to scroll through all units that are in the Override Mode.

Overrides Screen

Loop = 1 Unit = 59

OVERRIDE FOUND