10.7.- MBUS COMMUNICATIONS

general features

Maximum power of the module

2 W

Communications

Bus

Wired M-Bus

Protocol

Slave M-Bus compatible to EN 13757-2 and EN 13757-3

Baud rate

1200 - 2400 - 4800 - 9600

Primary address

1 ... 250

Stop bits

1

Parity

even

environmental features

Operating temperature

-10ºC ... +50ºC

Storage temperature

-20ºC ... +80ºC

Relative humidity (without condensation)

5 ... 95%

Maximum altitude

2000 m

Protection degree

IP30

Mechanical features

Dimensions (mm)

figure 215 and figure 216

Weight

80 g

enclosure

V0 self-extinguishing plastic

Assembly

Panel

Standards

Safety requirements for electrical equipment for measurement, control

and laboratory use

IEC 61010: 2010

electromagnetic compatibility (CeM)� Part 6-2: generic standards� Immu-

nity for industrial environments�

UNE-EN 6100-6-2:2006

electromagnetic compatibility (CeM)� Part 6-4: generic standards� emis-

sions standard for industrial environments�

UNE-EN 6100-6-4:2007

Coordination of the insulation of units installed in low voltage systems

(networks)

IEC 664: 2007

Information technology equipment� Radio disturbance characteristics�

Limits and methods of measurement�

UNE-EN 55022

Communication systems for and remote reading of meters - Part 2: Physi-

cal and link layer

UNE-EN 13757-2:2004

Communication systems for and remote reading of meters - Part 3: Dedi-

cated application layer

UNE-EN 13757-3:2004

Heat Meters - Part 3: Data exchange and interfaces

UNE-EN 1434-3:2008