10.7.- MBUS COMMUNICATIONS
general features
Maximum power of the module
2 W
Communications
Bus
Wired M-Bus
Protocol
Slave M-Bus compatible to EN 13757-2 and EN 13757-3
Baud rate
1200 - 2400 - 4800 - 9600
Primary address
1 ... 250
Stop bits
1
Parity
even
environmental features
Operating temperature
-10ºC ... +50ºC
Storage temperature
-20ºC ... +80ºC
Relative humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Protection degree
IP30
Mechanical features
Dimensions (mm)
figure 215 and figure 216
Weight
80 g
enclosure
V0 self-extinguishing plastic
Assembly
Panel
Standards
Safety requirements for electrical equipment for measurement, control
and laboratory use
IEC 61010: 2010
electromagnetic compatibility (CeM)� Part 6-2: generic standards� Immu-
nity for industrial environments�
UNE-EN 6100-6-2:2006
electromagnetic compatibility (CeM)� Part 6-4: generic standards� emis-
sions standard for industrial environments�
UNE-EN 6100-6-4:2007
Coordination of the insulation of units installed in low voltage systems
(networks)
IEC 664: 2007
Information technology equipment� Radio disturbance characteristics�
Limits and methods of measurement�
UNE-EN 55022
Communication systems for and remote reading of meters - Part 2: Physi-
cal and link layer
UNE-EN 13757-2:2004
Communication systems for and remote reading of meters - Part 3: Dedi-
cated application layer
UNE-EN 13757-3:2004
Heat Meters - Part 3: Data exchange and interfaces
UNE-EN 1434-3:2008