beautypg.com

CIRCUTOR CVM-B Series User Manual

Page 239

background image

Table 103: Modbus memory map: Status of digital inputs (Table 4)�

Status of digital inputs: Slot 4

Configuration variable

Address

Valid data window

Input Status 1

D160 - D161

0 to 1

Input Status 2

D162 - D163

0 to 1

Input Status 3

D164 - D165

0 to 1

Input Status 4

D166 - D167

0 to 1

Input Status 5

D168 - D169

0 to 1

Input Status 6

D16A - D16B

0 to 1

Input Status 7

D16C - D16D

0 to 1

Input Status 8

D16E - D16F

0 to 1

7�3�4�5�- Status of transistor digital outputs

The following functions are implemented for these variables:

function 0x04: reading registers.

Table 104:Modbus memory map: Status of transistor digital outputs (Table 1)�

Status of transistor digital outputs

Configuration variable

Valid data window

Alarm

Impulse

output

Alarm

Impulse

output

Latch

(1)

kWh or Wh

0: unlock alarm

1: locked alarm

kWh or Wh energy meter

Delay in the connection

(2)

Wh or mWh

Energy meter which indicates

the value of the connection

delay variable (ON)

Wh or mWh energy meter

Delay in the disconnection

(2)

Energy

meter

factor

Energy meter which indicates

the value of the disconnection

delay variable (OFF)

Energy meter factor meter

Alarm activation date: Year

(2)

-

2013 to 2076

-

Alarm activation date: Month

(2)

-

1 to 12

-

Alarm activation date: Day

(2)

-

1 to 31

-

Alarm activation time: Hour

(2)

-

0 to 23

-

Alarm activation time: Minutes

(2)

-

0 to 59

-

Alarm activation time: Seconds

(2)

-

0 to 59

-

Not used

-

-

Not used

-

-

Status

(2)

0: No alarm,

1: Active alarm,

Alarm status

(2)

0: No alarm,

1: Pre-alarm,

2: Connection or disconnection delay,

3: Alarm,

4: Impulses.

(1)

If the latch option has been programmed in an alarm and it has been activated, the alarm will be unlocked with

this option.

(2)

For these variables only

function 0x04 is implemented: reading registers.

239

Instruction Manual

CVM-B100 - CVM-B150