beautypg.com

CIRCUTOR CVM-B Series User Manual

Page 220

background image

7�2�4�1�- Programming of relay digital outputs

The following functions are implemented for these variables:

function 0x04: reading registers.

function 0x10: Writing multiple registers.

Table 68: Modbus memory map: Relay digital outputs, expansion modules (Table 1)�

Configuration of relay digital outputs

Configuration variable

Valid data window

Default value

Variable code

Table 21

0

Pre-alarm value

0 to 100%

0

Minimum value

(1)

Table 44

0

Maximum value

(1)

Table 44

0

Connection delay (ON)

0 to 999 s.

0

Disconnection delay (OFF)

0 to 999 s.

0

Latch

0 : Unlocked

1: Locked

0

Output status

0 : Normally open

1: Normally closed

0

Module no.

0

0

(1)

When programming the maximum and minimum values, the decimals for the variable selected must be included

.

Table 69: Modbus memory map: Relay digital outputs, expansion modules (Table 2)�

Configuration of relay digital outputs: Slot 1

Configuration variable

Address

Output

1

Output

2

Output

3

Output

4

Output

5

Output

6

Output

7

Output

8

Maximum value

C350

C364

C378

C38C

C3A0

C3B4

C3C8

C3DC

Minimum value

C352

C366

C37A

C38E

C3A2

C3B6

C3CA

C3DE

Delay connection (ON)

CE54

C368

C37C

C390

C3A4

C3B8

C3CC

C3E0

Disconnection delay (OFF)

C355

C369

C37D

C391

C3A5

C3B9

C3CD

C3E1

Pre-alarm value

C356

C36A

C37E

C392

C3A6

C3BA

C3CE

C3E2

Output status

C357

C36B

C37F

C393

C3A7

C3BB

C3CF

C3E3

Latch

C358

C36C

C380

C394

C3A8

C3BC

C3D0

C3E4

Not used

C359

C36D

C381

C395

C3A9

C3BD

C3D1

C3E5

Variable code

C35A

C36E

C382

C396

C3AA

C3BE

C3D2

C3E6

Module no.

C35B

C36F

C383

C397

C3AB

C3BF

C3D3

C3E7

Note: The 12 registers must be written and read at once (as a group), otherwise it will respond

with an error.

220

CVM-B100 - CVM-B150

Instruction Manual