CIRCUTOR CVM-B Series User Manual
Page 220
7�2�4�1�- Programming of relay digital outputs
The following functions are implemented for these variables:
function 0x04: reading registers.
function 0x10: Writing multiple registers.
Table 68: Modbus memory map: Relay digital outputs, expansion modules (Table 1)�
Configuration of relay digital outputs
Configuration variable
Valid data window
Default value
Variable code
Table 21
0
Pre-alarm value
0 to 100%
0
Minimum value
(1)
0
Maximum value
(1)
0
Connection delay (ON)
0 to 999 s.
0
Disconnection delay (OFF)
0 to 999 s.
0
Latch
0 : Unlocked
1: Locked
0
Output status
0 : Normally open
1: Normally closed
0
Module no.
0
0
(1)
When programming the maximum and minimum values, the decimals for the variable selected must be included
.
Table 69: Modbus memory map: Relay digital outputs, expansion modules (Table 2)�
Configuration of relay digital outputs: Slot 1
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Maximum value
C350
C364
C378
C38C
C3A0
C3B4
C3C8
C3DC
Minimum value
C352
C366
C37A
C38E
C3A2
C3B6
C3CA
C3DE
Delay connection (ON)
CE54
C368
C37C
C390
C3A4
C3B8
C3CC
C3E0
Disconnection delay (OFF)
C355
C369
C37D
C391
C3A5
C3B9
C3CD
C3E1
Pre-alarm value
C356
C36A
C37E
C392
C3A6
C3BA
C3CE
C3E2
Output status
C357
C36B
C37F
C393
C3A7
C3BB
C3CF
C3E3
Latch
C358
C36C
C380
C394
C3A8
C3BC
C3D0
C3E4
Not used
C359
C36D
C381
C395
C3A9
C3BD
C3D1
C3E5
Variable code
C35A
C36E
C382
C396
C3AA
C3BE
C3D2
C3E6
Module no.
C35B
C36F
C383
C397
C3AB
C3BF
C3D3
C3E7
Note: The 12 registers must be written and read at once (as a group), otherwise it will respond
with an error.
220
CVM-B100 - CVM-B150
Instruction Manual