7�4�4�2�- Programming analogue inputs

The following functions are implemented for these variables:

function 0x04: reading registers.

function 0x10:Writing multiple registers.

Table 116:Modbus memory map: Analogue inputs, expansion modules (Table 1)�

Configuration of analogue inputs

Configuration variable

Valid data window

Default value

Scale

0: 0 to 20 mA

1: 4 to 20 mA

0

Zero

-32000 to 32000

0

Full-scale

-32000 to 32000

20000

No. of decimals

0 to 5

0

Input name

(1)

8 characters

“--”

Units

(1)

5 characters

“--”

(1)

the characters must be sent in hexadecimal.

Table 117: Modbus memory map: Analogue inputs, expansion modules (Table 2)�

Configuration of analogue inputs: Slot 1

Configuration variable

Address

Input 1

Input 2

Input 3

Input 4

Zero

D2F0

D304

D318

D32C

Full-scale

D2F1

D305

D319

D32D

Scale

D2F2

D306

D31A

D32E

No. of decimals

D2F3

D307

D31B

D32F

Input name

D2F4 - D2F7 D308 - D30B

D31C - D31F D330 - D333

Units

D2F8 - D2FA D30C - D30E

D320 - D322

D334 - D336

Note: The 11 registers must be written and read at once (as a group), otherwise it will respond

with an error.

Table 118: Modbus memory map: Analogue inputs, expansion modules (Table 3)�

Configuration of analogue inputs: Slot 2

Configuration variable

Address

Input 1

Input 2

Input 3

Input 4

Zero

D6D8

D6EC

D700

D714

Full-scale

D6D9

D6ED

D701

D715

Scale

D6DA

D6EE

D702

D716

No. of decimals

D6DB

D6EF

D703

D717

Input name

D6DC - D6DF D6F0 - D6F3

D704 - D707

D718 - D71B

Units

D6E0 - D6E2

D6F4 - D6F6

D708 - D70A D71C - D71E

Note: The 11 registers must be written and read at once (as a group), otherwise it will respond

with an error.

256

CVM-B100 - CVM-B150

Instruction Manual