CIRCUTOR CVM-B Series User Manual
Page 202

6�3�8�5�- Alarm status
6�3�8�5�1�- Relay digital outputs
The
Latch variable occupies 2 registers.
All other variables
occupy 1 register each.
Table 63: Modbus memory map: Alarm status: Relay digital outputs:
Alarm status Relay digital outputs
Configuration variable
Address
Valid data window
Output 1
Output 2
Latch
(1)
7558-7559
756C-756D
0: unlock alarm
1: locked alarm
Connection delay
(2)
755A
756E
Energy meter which indicates the value of
the connection delay variable (ON)
Disconnection delay
(2)
755B
756F
Energy meter which indicates the value of
the disconnection delay variable (OFF)
Alarm activation date: Year
(2)
755C
7570
2013 to 2076
Alarm activation date: Month
(2)
755D
7571
1 to 12
Alarm activation date: Day
(2)
755E
7572
1 to 31
Alarm activation time: Hour
(2)
755F
7573
0 to 23
Alarm activation time: Minutes
(2)
7560
7574
0 to 59
Alarm activation time: Seconds
(2)
7561
7575
0 to 59
Not used
7562
7576
-
Not used
7563
7577
-
Status
(2)
7564
7578
0: No alarm,
1: Active alarm
Alarm status
(2)
7564
7578
0: No alarm,
1: Pre-alarm,
2: Connection or disconnection delay,
3: Alarm,
4: Impulses,
(1)
If the latch option has been programmed in an alarm and it has been activated, the alarm will be unlocked with
this option.
(2)
For these variables only
function 0x04 is implemented: reading registers.
Note: The 14 registers must be written at once (as a group), otherwise it will respond with an
error.
202
CVM-B100 - CVM-B150
Instruction Manual