Maximum demand variables – CIRCUTOR CVM-B Series User Manual
Page 184
Table 25 ( Continuation ) : Modbus memory map: current energy variables�
Parameter
Symbol
Address
1
(1)
2
(1)
Capacitive reactive energy generated L1
kvarhC L1 (-)
6D0-6D1
6D2
Capacitive reactive energy generated L2
kvarhC L2 (-)
6D3-6D4
6D5
Capacitive reactive energy generated L3
kvarhC L3 (-)
6D6-6D7
6D8
Capacitive reactive energy generated LIII
kvarhC LIII (-)
6D9-6DA
6DB
Reactive energy generated L1
kvarh L1 (-)
6DC-6DD
6DE
Reactive energy generated L2
kvarh L2 (-)
6DF-6E0
6E1
Reactive energy generated L3
kvarh L3 (-)
6E2-6E3
6E4
Reactive energy generated LIII
kvarh LIII (-)
6E5-6E6
6E7
Apparent energy generated L1
kVAh L1 (-)
6E8-6E9
6EA
Apparent energy generated L2
kVAh L2 (-)
6EB-6EC
6ED
Apparent energy generated L3
kVAh L3 (-)
6EE-6EF
6F0
Apparent energy generated LIII
kVAh LIII (-)
6F1-6F2
6F3
(1)
Note :The energy units are at address 0x1580.
Format of the units: Power of 10 (with sign).
Unit (Register 0x1580) = 0
→ Address 1: kW and Address 2: W
Unit (Register 0x1580) = -3
→ Address 1: W and Address 2: mW
6�3�3�- Maximum Demand Variables
For these variables
function 0x04 is implemented: reading registers.
Each instantaneous value occupies 2 registers.
The maximum values occupy 4 registers, 2 for the variable value while the next two indicate
the date and time when the maximum occurred, in compact format.
Table 26: Modbus memory map: Maximum Demand variables
Parameter
Tariff 1
Tariff 2
Tariff 3
Instantaneous Maximum Instantaneous Maximum Instantaneous Maximum
Current L1
A8C-A8D
D48-D4B
AA4-AA5
D78-D7B
ABC-ABD
DA8-DAB
Current L2
A8E-A8F
D4C-D4F
AA6-AA7
D7C-D7F
ABE-ABF
DAC-DAF
Current L3
A90-A91
D50-D53
AA8-AA9
D80-D83
AC0-AC1
DB0-DB3
Three-phase
current
A92-A93
D54-D57
AAA-AAB
D84-D87
AC2-AC3
DB4-DB7
Active Power L1
A94-A95
D58-D5B
AAC-AAD
D88-D8B
AC4-AC5
DB8-DBB
Active Power L2
A96-A97
D5C-D5F
AAE-AAF
D8C-D8F
AC6-AC7
DBC-DBF
Active Power L3
A98-A99
D60-D63
AB0-AB1
D90-D93
AC8-AC9
DC0-DC3
Active three-phase
power
A9A-A9B
D64-D67
AB2-AB3
D94-D97
ACA-ACB
DC4-DC7
ApparentPower L1
A9C-A9D
D68-D6B
AB4-AB5
D98-D9B
ADC-ACD
DC8-DCB
Apparent
Power L2
A9E-A9F
D6C-D6F
AB6-AB7
D9C-D9F
ACE-ACF
DCC-DCF
Apparent
Power L3
AA0-AA1
D70-D73
AB8-AB9
DA0-DA3
AD0-AD1
DD0-DD3
Three-phase
Apparent Power
AA2-AA3
D74-D77
ABA-ABB
DA4-DA7
AD2-AD3
DD4-DD7
Note The voltage units are at address 0x157D and the power units at address 0x1580. Format
of the units: Power of 10 (with sign).
184
CVM-B100 - CVM-B150
Instruction Manual