Modbus communications – CIRCUTOR CVM-B Series User Manual
Page 267

7�5�5�- MODBUS COMMUNICATIONS
The following functions are implemented for these variables:
function 0x04: reading registers.
function 0x10: Writing multiple registers.
7.5.5.1.- Configuration of DHCP activation/deactivation
Table 127:Modbus memory map: Modbus TCP (Bridge) communications module (Table 1)
Configuration of DHCP activation/deactivation
Configuration variable
Address
Valid data margin
Default value
DHCP Flag
F23A
0 : Deactivation
1: Activation
1
7.5.5.2.- Configuration of the TCP parameters
Table 128:Modbus memory map: Modbus TCP (Bridge) communications module (Table 2)
Configuration of the Modbus TCP parameters
Configuration variable
Address
Valid data margin
Default value
IP Address
F230 - F231
1 long : 4 characters
-
Subnet Mask
F232 - F233
1 long : 4 characters
-
Gateway
F234 - F235
1 long : 4 characters
-
Note: The module resets to activate the configuration.
Note: The 6 registers must be written at once (as a group), otherwise it will respond with an
error.
7.5.5.3.- Configuration of the RS-485 gateway parameters
Table 129:Modbus memory map: Modbus TCP (Bridge) communications module (Table 3)
Configuration of the Modbus TCP parameters
Configuration variable
Address
Valid data margin
Default value
Baud rate
F500
0: 1200 - 1: 2400 - 2: 4800 -
3: 9600 - 4: 19200 - 5: 38400 -
6: 57600 - 7: 76800 - 8: 115200
4
Parity
F501
0 : No parity
1: Odd parity
2: Even parity
0
Length
F502
1: 8-bit
1
Stop Bits
F503
0: 1 stop bit
1: 2 stop bits
0
Note: The 4 registers must be written at once (as a group), otherwise it will respond with an
error.
7�5�5�4�- MAC address of the Modbus TCP module
The function implemented for this variable is:
function 0x04: reading registers.
Table 130:Modbus memory map: Modbus TCP (Bridge) communications module (Table 4)
MAC address of the Modbus TCP module
Configuration variable
Address
Valid data margin
MAC address
F236 - F238
3 integers : 6 characters
267
Instruction Manual
CVM-B100 - CVM-B150