6�3�8�- Other unit variables

6�3�8�1�- firmware version

These parameters occupy 6 registers.

Table 59: Modbus memory map: firmware version�

firmware version

(1)

Configuration variable

Address

example

Version

2AF8 – 2AFD

“010102”

(1)

For this variable only

function 0x04 is implemented: reading registers.

The firmware version is provided in an ASCII 6 character string.

6�3�8�2�- Date of last calibration

These parameters occupy 1 register each.

Table 60:Modbus memory map: Date of last calibration�

Date of last calibration

(1)

Configuration variable

Address

Valid data window

Day

2844

1 to 31

Month

2845

1 to 12

Year

2846

2013 to 2076

Time

2847

0 to 23

Minutes

2848

0 to 59

Seconds

2849

0 to 59

(1)

For these variables only

function 0x04 is implemented: reading registers.

6�3�8�3�- Internal temperature

These parameters occupy 2 registers.

Table 61:Modbus memory map: Internal temperature�

Internal temperature

(1)

Configuration variable

Address

Valid data window

Internal temperature

2852-2853

ºC with 2 decimals

(1)

For this variable only

function 0x04 is implemented: reading registers.

6�3�8�4�- Status of digital inputs

The

Input Status 1 and Input Status 2 variables occupy 2 registers.

The

Current tariff variable occupies 1 register.

Table 62: Modbus memory map: Status of digital inputs�

Status of digital inputs, mode: Logic state

(1)

Configuration variable

Address

Valid data window

Input Status 1

59D8 – 59D9

0 to 1

Input Status 2

59DA – 59DB

0 to 1

Status of digital inputs, mode: Logic state

(1)

Current tariff

59DC

0: Tariff 1

1:Tariff 2

2: Tariff 3

(1)

For these variables only

function 0x04 is implemented: reading registers.