7�3�4�2�- Manual programming of transistor digital outputs

The following functions are implemented for these variables:

function 0x04:reading registers.

function 0x10: Writing multiple registers.

Table 90: Modbus memory map: Manual programming of outputs, expansion modules (Table 1)�

Manual programming of transistor digital outputs

Configuration variable

Valid data window

Default value

Programming status

(1)

0: Automatic

1:Manual

0

Value

0: Open

1:Closed

0

(1)

When programming the

Programming status manually set the output for the transistors manually, using the

Value parameter. The configuration of the transistor digital outputs programmed in the unit no longer works.
The transistors work in automatic mode according to the configuration programmed in the unit.

Table 91: Modbus memory map: Manual programming of outputs, expansion modules (Table 2)�

Manual programming of transistor digital outputs: Slot 1

Configuration variable

Address

Output

1

Output

2

Output

3

Output

4

Output

5

Output

6

Output

7

Output

8

Programming status

C428

C43C

C450

C464

C478

C48C

C4A0

C4B4

Value

C429

C43D

C451

C465

C479

C48D

C4A1

C4B5

Note: The 2 registers must be written at once (as a group), otherwise it will respond with an

error.

Table 92: Modbus memory map: Manual programming of outputs, expansion modules (Table 3)�

Manual programming of transistor digital outputs: Slot 2

Configuration variable

Address

Output

1

Output

2

Output

3

Output

4

Output

5

Output

6

Output

7

Output

8

Programming status

C810

C824

C838

C84C

C874

C874

C888

C89C

Value

C811

C825

C839

C84D

C875

C875

C889

C89D

Note: The 2 registers must be written at once (as a group), otherwise it will respond with an

error.

Table 93: Modbus memory map: Manual programming of outputs, expansion modules (Table 4)�

Manual programming of transistor digital outputs: Slot 3

Configuration variable

Address

Output

1

Output

2

Output

3

Output

4

Output

5

Output

6

Output

7

Output

8

Programming status

CBF8

CC0C

CC20

CC34

CC48

CC5C

CC70

CC84

Value

CBF9

CC0d

CC21

CC35

CC49

CC5D

CC71

CC85

Note: The 2 registers must be written at once (as a group), otherwise it will respond with an

error.