Deleting parameters – CIRCUTOR CVM-B Series User Manual

Page 204

background image

6�3�8�6� energy closes

The

Energy variables occupy 90 registers.

All other variables

occupy 1 register each.

energy closes

Variable

(1)

Address

1 day active energy close

2BC0 - 2C19

1 day reactive energy close total

2C24 - 2C7D

Index of the sample from the close of the day

(2)

2C7E

1 week active energy close

2C88 - 2CE1

1 week reactive energy close total

2CEC - 2D45

Index of the sample from the close of the week

(2)

2D46

1 month active energy close

2D50-2DA9

1 month reactive energy close total

2DB4 - 2E0D

Index of the sample from the close of the month

(2)

2E0E

Active energy at 1 year close

2E18 - 2E71

Total reactive energy at 1 year close

2E7C - 2ED5

Index of the sample of the following year close

(2)

2ED6

(1)

For these variables the

function 0x04 is implemented: reading registers.

(2)

The information in the index of the sample of the following year close is provided in order to know in what position

the registers are currently at, bearing in mind that this position is still empty and will be the next to be filled in when
the next close is made.

The registers have information on the energy at the moment of the close.

The close is calculated as the difference between the most recent energy value and the energy

logged in the previous period.

Note: The 90 registers must be written at once (as a group), otherwise it will respond with an

error.

6�3�9�- Deleting parameters

These parameters occupy 1 register each.

Parameters can be deleted using

function 0x05: writing a relay.

Table 65:Modbus memory map: Deleting parameters

Deleting parameters

Address

Value to be sent

System reset

07D0

0x00FF

Deleting energies

0834

0x00FF

Deleting maximum and minimum values

0837

0x00FF

Deleting of partial meter of tariff 1 energy consumed

0838

0x00FF

Deleting of partial meter of tariff 2 energy consumed

0839

0x00FF

Deleting of partial meter of tariff 3 energy consumed

083A

0x00FF

Deleting of partial meter of tariff 1 energy generated

083B

0x00FF

Deleting of partial meter of tariff 2 energy generated

083C

0x00FF

Deleting of partial meter of tariff 3 energy generated

083D

0x00FF

Initialises Maximum Demand

083E

0x00FF

Deleting of Maximum Demand maximum and minimum values

083F

0x00FF

204

CVM-B100 - CVM-B150

Instruction Manual