CIRCUTOR CVM-B Series User Manual
Page 192

6�3�7�9�- Installation data
These parameters occupy 1 register each.
Table 40: Modbus memory map: Configuration variables (Installation data)
Installation data
Configuration variable
Address
Valid data window
Default value
Nominal Frequency
(1)
2720
5000 or 6000
5000
Number of quadrants
2722
2 or 4
4
(1)
The units of the frequency are at address 0x157F. Format of the units: Power of 10 (with sign).
6�3�7�10�- Cost of energy consumption and generation
The
Cost configuration variables occupy 2 registers each.
The
Currency configuration variables occupy 4 registers.
Table 41:Modbus memory map: Configuration variables (Energy cost)
energy cost
Configuration variable
Address
Valid data window
Default value
Cost per kWh of tariff 1 consumption
27D8-27D9
0 to 100
(1)
0
Cost per kWh of tariff 2 consumption
27DA-27DB
0 to 100
(1)
0
Cost per kWh of tariff 3 consumption
27DC-27DD
0 to 100
(1)
0
Cost per kWh of tariff 1 generation
27DE-27DF
0 to 100
(1)
0
Cost per kWh of tariff 2 generation
27E0-27E1
0 to 100
(1)
0
Cost per kWh of tariff 3 generation
27E2-27E3
0 to 100
(1)
0
Currency
27E4-27E7
7 ascii characters
EURO
(1)
The number of decimals are indicated at address
0x1586. Format of the units: Power of 10 (with sign).
Note: The 16 registers must be written and read at once (as a group), otherwise it will respond
with an error.
6�3�7�11�- CO
2
consumption and generation emissions
These parameters occupy 2 registers each.
Table 42:Modbus memory map: Configuration variables (CO
2
emissions)
C0
2
emissions
Configuration variable
Address
Valid data window
Default value
Tariff 1 consumption emissions ratio
2774-2775
0 to 100
(1)
0
Tariff 2 consumption emissions ratio
2776-2777
0 to 100
(1)
0
Tariff 3 consumption emissions ratio
2778-2779
0 to 100
(1)
0
Tariff 1 generation emissions ratio
277A-277B
0 to 100
(1)
0
Tariff 2 generation emissions ratio
277C-277D
0 to 100
(1)
0
Tariff 3 generation emissions ratio
277E-277F
0 to 100
(1)
0
(1)
The number of decimals are indicated at address
0x1585. Format of the units: Power of 10 (with sign)
.
Note: The 12 registers must be written at once (as a group), otherwise it will respond with an
error.
192
CVM-B100 - CVM-B150
Instruction Manual