CIRCUTOR CVM-B Series User Manual
Page 222

Table 72:Modbus memory map: Relay digital outputs, expansion modules (Table 5)�
Configuration of relay digital outputs: Slot 4
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Maximum value
CF08
CF1C
CF30
CF44
CF58
CF6C
CF80
CF94
Minimum value
CF0A
CF1E
CF32
CF46
CF5A
CF6E
CF82
CF96
Delay connection (ON)
CF0C
CF20
CF34
CF48
CF5C
CF70
CF84
CF98
Disconnection delay (OFF)
CF0D
CF21
CF35
CF49
CF5D
CF71
CF85
CF99
Pre-alarm value
CF0E
CF22
CF36
CF4A
CF5E
CF72
CF86
CF9A
Output status
CF0F
CF23
CF37
CF4B
CF5F
CF73
CF87
CF9B
Latch
CF10
CF24
CF38
CF4C
CF60
CF74
CF88
CF9C
Not used
CF11
CF25
CF39
CF4D
CF61
CF75
CF89
CF9D
Variable code
CF12
CF26
CF3A
CF4E
CF62
CF76
CF8A
CF9E
Module no.
CF13
CF27
CF3B
CF4F
CF63
CF77
CF8B
CF9F
Note: The 12 registers must be written and read at once (as a group), otherwise it will respond
with an error.
7�2�4�2�-
Manual programming of relay digital outputs
The following functions are implemented for these variables:
function 0x04: reading registers.
function 0x10: Writing multiple registers.
Table 73: Modbus memory map: Manual programming of outputs, expansion modules (Table 1)�
Manual programming of relay digital outputs
Configuration variable
Valid data window
Default value
Programming status
(1)
0: Automatic
1:Manual
0
Value
0: Open
1:Closed
0
(1)
When programming the
Programming status manually set the output for the relays manually, using the Value
parameter. The configuration of the relay digital outputs programmed in the unit no longer works.
The relays work in automatic mode according to the configuration programmed in the unit.
Table 74: Modbus memory map: Manual programming of outputs, expansion modules (Table 2)�
Manual programming of relay digital outputs: Slot 1
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Programming status
C428
C43C
C450
C464
C478
C48C
C4A0
C4B4
Value
C429
C43D
C451
C465
C479
C48D
C4A1
C4B5
Note: The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
222
CVM-B100 - CVM-B150
Instruction Manual