6�3�7�5�- Measurement connection mode
This parameter occupies 1 register.
Table 35: Modbus memory map: Configuration variables (Measurement connection mode).
Measurement connection mode
Configuration variable
Address
Valid data window
Default value
Measurement connection mode
2A9D
0: Single-phase
1: Two-phase
2: Two-phase with Neutral
3: Three-phase
4: Three-phase with Neutral
5: Aron
4
6�3�7�6�- Ratio of voltage and current transformers
These parameters occupy 2 registers each.
Table 36:Modbus memory map: Configuration variables (transformation ratios)
Transformation ratios
Configuration variable
Address
Valid data window
Default value
Primary voltage
(1) (2)
2710-2711
1 - 500000
1
Secondary voltage
(1)(4)
2712-2713
1 - 9999
10
Primary current
(2)
2714-2715
Minimum value:
1
Maximum value:
../1A y ../5 A:
10000
../ 0.250 A:
1500
5
Secondary current
2716-2717
1 : ../1A
5 : ../5 A
250 : ../ 0.250 A
5
Primary neutral current
2718-2719
1 - 10000
5
Secondary neutral current
271A-271B
0: Calculated current
1 : ../1A
5 : ../5 A
5
Rated voltage
(3)
271C-271D
Minimum value:
(Rated Voltage / Voltage ratio
(5)
)
≥ 50
Maximum value:
(Rated Voltage / Voltage ratio
(5)
)
≤ 1000
230.00
(1)
Primary voltage/Secondary voltage must not exceed the value 9999.
(2)
Primary voltage * Primary current must not exceed the value 60MW.
(3)
It has 2 decimals.
(4)
The secondary voltage has 1 decimal.
(5)
The voltage ratio is the ratio between the primary and secondary voltage.
Note: The 14 registers must be written at once (as a group), otherwise it will respond with an
error.