6�2�1�- example of MODBUS query
Query: Instantaneous value of the L1 phase voltage
Address
function
Initial reg-
ister
No� of regis-
ters
CRC
0A
04
0000
0002
70B0
Address: 0A, Peripheral number: 10 in decimal.
function: 04, Read function.
Initial Register: 0000, register from which to start reading.
No� of registers: 0002, number of registers to be read.
CRC: 70B0, CRC character.
Response:
Address
function
No� of
Bytes
Register
no� 1
Register
no� 2
CRC
0A
04
04
0000
084D
8621
Address: 0A, Responding peripheral number: 10 in decimal.
function: 04, Read function.
No� of bytes: 04, No. of bytes received.
Register: 0000084D, value of the L1 phase voltage: VL1 x 10: 212.5 V
CRC: 8621, CRC character.
6.3.- MODBUS MEMORY MAP
All
MODBUS map addresses are hexadecimal.
6�3�1�- Measurement Variables
For these variables
function 0x04 is implemented: reading registers.
Each instantaneous value occupies 2 registers.
The maximum and minimum values occupy 4 registers, 2 for the variable value while the next
two indicate the date and time when the maximum or minimum value was read, in compact
format (U32).
The short format of the register date and time is:
Bit
32
Bits
31 ��� 27
Bits
26���23
Bits
22���18
Bits
17���13
Bits
12���7
Bits
6���1
x
Year
Month
Day
Hour
Minutes
seconds
The year is calculated with the offset = 2013, that is the
Real Year : 2013 + Year ( bits 31 ...27) .
Each unit occupies a separate register.
178
CVM-B100 - CVM-B150
Instruction Manual