6.3.7.- Unit configuration variables
The following functions are implemented for these variables:
function 0x04: reading registers.
function 0x10: Writing multiple registers.
NB: The programming values must be written in hexadecimal.
It is necessary to change the screen when a setup change is made for communi-
cations in order for the changes take effect in the display.
6�3�7�1�- Date and time
These parameters occupy 1 register each.
Table 30:Modbus memory map: Configuration variables (Date and Time).
Date and Time
Configuration variable
Address
Valid data window
Default value
Year
283C
2013 to 2076
-
Month
283D
1 to 12
-
Day
283E
1 to 31
-
Time
283F
0 to 23
-
Minutes
2840
0 to 59
-
Seconds
2841
0 to 59
-
Note: The 6 registers must be written at once (as a group), otherwise it will respond with an
error
.
6�3�7�2�- Time zone
These parameters occupy 1 register each.
Table 31:Modbus memory map: Configuration variables (time zone).
Local time configuration
Configuration variable
Address
Valid data window
Default value
Configuration of local time
2A9E
Table 32
0
Time
2A9F
0: Winter
1:Summer
0
Note: The 2 registers must be written at once (as a group), otherwise it will respond with an
error.