7�3�4�- COMUNICACIONeS MODBUS
The address of the Modbus memory map depends on the position of the expansion module in
the unit.
Slot 1 will be the position of the expansion module installed just behind the standard unit, and
Slot 2 the next position...
As the maximum number of expansion modules that can be connected to the unit is 4, there
will only be 4 slots.
7�3�4�1� - Programming of transistor digital outputs
The following functions are implemented for these variables:
function 0x04: reading registers.
function 0x10: Writing multiple registers.
Table 85: Modbus memory map: Transistor digital outputs, expansion modules (Table 1)�
Configuration of Transistor Digital Outputs
Configuration variable
Valid data window
Default
value
Variable code
Table 21
0
Alarm
Impulse output
0 to 100%
0
Pre-alarm value
-
Minimum value
(1)
-
0
Maximum value
(1)
Energy meter factor
0
Connection delay (ON)
High period
(2)
Alarm
Impulse output
0
0 to 999 s.
1 to 65536
Disconnection delay (OFF)
Low period
(2)
0 to 999 s.
1 to 65536
0
Latch
-
0 : Unlocked
1: Locked
0
Output status
-
0 : Normally open
1: Normally closed
0
Module no.
0
0
(1)
When programming the maximum and minimum values, the decimals for the variable selected must be included.
(2)
The programmed value is a multiple of 10 ms, when programming 1 the impulse will be at its minimum value of
10 ms.