integrated communications – CIRCUTOR CVM-B Series User Manual
Page 167
5�6�18�-
Integrated communications�
Select the RS-485 communications protocol and configuration parameters on the integrated
communications configuration screen,
.
The possible communications protocols are:
Modbus.
BACnet.
Using the keys
and
firstly select the communications protocol.
To confirm the selection, press the key
.
Integrated communications configuration parameters change according to the communications
protocol.
If no key is pressed for 5 minutes, the display screen changes automatically to the default
screen, which displays the voltage measurement of 4 parameters.
5�6�18�1�-
Configuration parameters, Modbus protocol.
When selecting the Modbus communications protocol,
, you can program the
following parameters:
The peripheral number.
The transmission speed, Baud Rate.
The parity.
The number of stop bits.
figure 137: Integrated communications configuration screen (Modbus protocol).
167
Instruction Manual
CVM-B100 - CVM-B150