beautypg.com

Connection terminals, Leds – CIRCUTOR CVM-B Series User Manual

Page 259

background image

7.5.- MODBUS/TCP BRIDGE COMMUNICATIONS MODULE

The

M-CVM-AB-Modbus TCP ( Bridge) is a communications module for connecting the

CVM-B units to a Modbus/TCP network and as an Ethernet to RS-485 gateway.

Modbus/TCP is a communications protocol designed for enabling industrial units to

communicate with each other on Ethernet networks using TCP/IP protocols.

Basically,

Modbus/TCP encapsulates a Modbus frame within a TCP frame, making it possible

to configure and monitor a unit via the Internet.

The communications module is also equipped with an RS-485 gateway.

7�5�1�- CONNeCTION TeRMINALS

Table 125:List of terminals, Modbus TCP ( Bridge ) communications module�

Terminals in the unit

1: Ethernet

3: B(-), RS-485

2: A(+), RS-485

4: S, GND for RS-485

1

4

2

3

figure 177: Modbus TCP ( Bridge) communications module terminals

7�5�2�- LeDs

Table 126: List of LeDs, Modbus TCP (Bridge) communications module�

LeD

Status

function

LINK / ACT

On

Unit connected to the network

Off

Unit disconnected from the network

Blinking light

Activity on the bus

SPeeD

On

100 BT

Off

10 BT

SPEED

LINK/ACT

figure 178: LeDs Modbus TCP� (Bridge)

259

Instruction Manual

CVM-B100 - CVM-B150