beautypg.com

CIRCUTOR CVM-B Series User Manual

Page 306

background image

(Continuation) Accuracy of measurements (in accordance with the IeC 61557-12 standard for

PMD SD/SS)

���/5A

���/1A

���/0�250A

Active energy measurement

(IEC 62053-22)

Class 0.5S

Class 1

Class 1

Reactive energy measurement

(IEC 62053-23)

Class 1

Class 2

Class 2

frequency measurement

Class 0.1

Class 0.1

Class 0.1

Power factor measurement

Class 0.5

Class 0.5

Class 0.5

Voltage THD measurement

Class 1

Class 1

Class 1

Voltage harmonics (up to 40th order)

Class 1

Class 1

Class 1

Current THD measurement

Class 1

Class 2

Class 2

Current harmonics (up to 40th order)

Class 1

Class 2

Class 2

Transistor digital outputs

Quantity

2

Type

Transistor

Maximum voltage

48V

Maximum current

130 mA

Maximum frequency

1 KHz

Pulse width

1 ms

Pulse duration (Ton / Toff)

0.3 ms / 0.7 ms

Relay digital outputs

Quantity

2

Maximum voltage, open contacts

250 V ~

Maximum current

6 A

Maximum switching power

1500 W (AC1)

electrical working life (at full load)

3x10

4

cycles

Mechanical working life

1x10

7

cycles

Digital inputs

Quantity

2

Type

Potential-free contact

Insulation

4 KV

Maximum short-circuit current

5 mA

Maximum voltage in open circuit

15 V

Modbus Communications

field bus

RS-485

Communications protocol

Modbus RTU

Speed

9600 - 19200 - 38400-57600-76800-115200

Stop bits

1 - 2

Parity

none - even - odd

BACnet communications

field bus

MS/TP

Communications protocol

BACnet

Speed

9600 - 19200 - 38400-57600-76800-115200

Stop bits

1

Parity

no parity

306