background image

10.6.- PROFIBUS COMMUNICATIONS

general features

Maximum power of the module

2 W

Communications

Connector

DB9

Protocol

Profibus

Identifier

4

Baud rate

19,2 kbs - 93,75 kbs - 187,5 kbs - 500 kbs - 1500 kbs -

3000 kbs - 6000 kbs - 12000 kbs

environmental features

Operating temperature

-10ºC ... +50ºC

Storage temperature

-20ºC ... +80ºC

Relative humidity (without condensation)

5 ... 95%

Maximum altitude

2000 m

Protection degree

IP30

Mechanical features

Dimensions (mm)

figure 215 and figure 216

Weight

80 g

enclosure

V0 self-extinguishing plastic

Assembly

Panel

Standards

Safety requirements for electrical equipment for measurement, control

and laboratory use

IEC 61010: 2010

electromagnetic compatibility (CeM)� Part 6-2: generic standards� Immu-

nity for industrial environments�

UNE-EN 6100-6-2:2006

electromagnetic compatibility (CeM)� Part 6-4: generic standards� emis-

sions standard for industrial environments�

UNE-EN 6100-6-4:2007

Coordination of the insulation of units installed in low voltage systems

(networks)

IEC 664: 2007

Information technology equipment� Radio disturbance characteristics�

Limits and methods of measurement�

UNE-EN 55022

314

CVM-B100 - CVM-B150

Instruction Manual