Relay digital inputs/outputs – CIRCUTOR CVM-B Series User Manual
Page 310

10.2.- RELAY DIGITAL INPUTS/OUTPUTS
general features
Maximum power of the module
3 W
Relay digital outputs
Quantity
8
Maximum voltage, open contacts
250 V~
Maximum current
3 A
Maximum switching power
750 VA
electrical working life (250 VAC / 3A)
10
5
cycles
Mechanical working life
2 x 10
7
cycles
Digital inputs
Quantity
8
Type
Potential-free contact
Insulation
4 kV
Input impedance
32 kΩ
environmental features
Operating temperature
-10ºC ... +50ºC
Storage temperature
-20ºC ... +80ºC
Relative humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Protection degree
IP30
Mechanical features
Dimensions (mm)
Weight
105 g
enclosure
V0 self-extinguishing plastic
Assembly
Panel
Standards
Safety requirements for electrical equipment for measurement, control
and laboratory use
IEC 61010: 2010
electromagnetic compatibility (CeM)� Part 6-2: generic standards� Immu-
nity for industrial environments�
UNE-EN 6100-6-2:2006
electromagnetic compatibility (CeM)� Part 6-4: generic standards� emis-
sions standard for industrial environments�
UNE-EN 6100-6-4:2007
Coordination of the insulation of units installed in low voltage systems
(networks)
IEC 664: 2007
Information technology equipment� Radio disturbance characteristics�
Limits and methods of measurement�
UNE-EN 55022
310
CVM-B100 - CVM-B150
Instruction Manual