Digital analogue inputs/outputs – CIRCUTOR CVM-B Series User Manual
Page 311
10.3.- DIGITAL ANALOGUE INPUTS/OUTPUTS
general features
Maximum power of the module
3W
Analogue outputs
Quantity
8
Maximum internal voltage
12 V
Linearity
<1%
DAC resolution
4096 dots
Analogue outputs in current mode
Nominal output range
0-20 mA or 4-20 mA (Programmable)
Maximum load resistor
300 Ω
Analogue outputs in voltage mode
Nominal output range
0-10 V
Minimum load resistor
5000 Ω
Analogue inputs
Quantity
4
Type of measurement
Current
Nominal input range
0-20 mA or 4-20 mA (Programmable)
Accuracy
<1%
Input impedance
150 Ω
Maximum acceptable input current
22 mA
environmental features
Operating temperature
-10ºC ... +50ºC
Storage temperature
-20ºC ... +80ºC
Relative humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Protection degree
IP30
Mechanical features
Dimensions (mm)
Weight
80 g
enclosure
V0 self-extinguishing plastic
Assembly
Panel
Standards
Safety requirements for electrical equipment for measurement, control
and laboratory use
IEC 61010: 2010
electromagnetic compatibility (CeM)� Part 6-2: generic standards� Immu-
nity for industrial environments�
UNE-EN 6100-6-2:2006
electromagnetic compatibility (CeM)� Part 6-4: generic standards� emis-
sions standard for industrial environments�
UNE-EN 6100-6-4:2007
Coordination of the insulation of units installed in low voltage systems
(networks)
IEC 664: 2007
Information technology equipment� Radio disturbance characteristics�
Limits and methods of measurement�
UNE-EN 55022
311
Instruction Manual
CVM-B100 - CVM-B150