Table 57, Table 56 – CIRCUTOR CVM-B Series User Manual
Page 200

Table 55 ( Continuation) : Configuration of custom screens: Variables�
Variables parameter
Variable
Value
Variable
Value
Apparent Power
0x000A
CO
2
Emissions
0x0018
Power Factor
0x000B
Cost
0x0019
Cosine
φ
0x000C
Empty (no parameters)
0x001A
Voltage THD
0x000D
Table 56: Configuration of custom screens: Phases.
Phases Parameter
Phase
Value
Phase
Value
L1
0x0000
L1-L2
0x0000
L2
0x0001
L2-L3
0x0001
L3
0x0002
L3-L1
0x0002
Total III
0x0003
L1-L2-L3
0x0003
LN
0x0004
Table 57:Configuration of custom screens: Tariffs
Tariffs Parameter
(7)
Tariff
Value
Tariff
Value
Tariff 1
0x0000
Tariff 3
0x0002
Tariff 2
0x0001
Total value of 3 tariffs
0x0003
(7)
If the variable has no tariff option, 00 will be sent.
6�3�7�19�- Manual programming of alarms
These parameters occupy 1 register each.
Table 58: Modbus memory map: Configuration variables (manual programming of alarms).
Manual programming of alarms
Configuration
variable
Address
Valid data window
Default
value
Output 1
Relay
Output 2
Relay
Output 1
Transistor
Output 1
Transistor
Programming status
(1)
4F20
4F34
4EF8
4F0C
0: Automatic
1:Manual
0
Value
4F21
4F35
4EF9
4F0D
0: Open
1:Closed
0
(1)
When programming the
Programming status manually , set the output for the relays and transistors manually,
using the
Value parameter. The configuration of the relay and transistor digital outputs programmed in the unit
no longer works.
The relays and transistors work in automatic mode according to the configuration programmed in the unit.
Note: The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
200
CVM-B100 - CVM-B150
Instruction Manual