CIRCUTOR CVM-B Series User Manual
Page 225

Table 79: Modbus memory map: Status of relay digital outputs (Table 2)�
Status of relay digital outputs: Slot 1
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Latch
C670
C684
C698
C6AC
C6C0
C6D4
C6E8
C6FC
Connection delay
C672
C686
C69A
C6AE
C6C2
C6D6
C6EA
C6FE
Disconnection delay
C673
C687
C69B
C6AF
C6C3
C6D7
C6EB
C6FF
Alarm activation date: Year
C674
C688
C69C
C6B0
C6C4
C6D8
C6EC
C700
Alarm activation date: Month
C675
C689
C69D
C6B1
C6C5
C6D9
C6ED
C701
Alarm activation date: Day
C676
C68A
C69E
C6B2
C6C6
C6DA
C6EE
C702
Alarm activation time: Time
C677
C68B
C69F
C6B3
C6C7
C6DB
C6EF
C703
Alarm activation time: Minutes
C678
C68C
C6A0
C6B4
C6C8
C6DC
C6F0
C704
Alarm activation time: Seconds
C679
C68D
C6A1
C6B5
C6C9
C6DD
C6F1
C705
Not used
C67A
C68E
C6A2
C6B6
C6CA
C6DE
C6F2
C706
Not used
C67B
C68F
C6A3
C6B7
C6CB
C6DF
C6F3
C707
Status
C67C
C690
C6A4
C6B8
C6CC
C6E0
C6F4
C708
Alarm status
C67D
C691
C6A5
C6B9
C6CD
C6E1
C6F5
C709
Note: The 14 registers must be written at once (as a group), otherwise it will respond with an
error.
Table 80: Modbus memory map: Status of relay digital outputs (Table 3)�
Status of relay digital outputs: Slot 2
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Latch
CA58
CA6C
CA80
CA94
CAA8
CABC
CAD0
CAE4
Connection delay
CA5A
CA6E
CA82
CA96
CAAA
CABE
CAD2
CAE6
Disconnection delay
CA5B
CA6F
CA83
CA97
CAAB
CABF
CAD3
CAE7
Alarm activation date: Year
CA5C
CA70
CA84
CA98
CAAC
CAC0
CAD4
CAE8
Alarm activation date: Month
CA5D
CA71
CA85
CA99
CAAD
CAC1
CAD5
CAE9
Alarm activation date: Day
CA5E
CA72
CA86
CA9A
CAAE
CAC2
CAD6
CAEA
Alarm activation time: Time
CA5F
CA73
CA87
CA9B
CAAF
CAC3
CAD7
CAEB
Alarm activation time: Minutes
CA60
CA74
CA88
CA9C
CAB0
CAC4
CAD8
CAEC
Alarm activation time: Seconds
CA61
CA75
CA89
CA9D
CAB1
CAC5
CAD9
CAED
Not used
CA62
CA76
CA8A
CA9E
CAB2
CAC6
CADA
CAEE
Not used
CA63
CA77
CA8B
CA9F
CAB3
CAC7
CADB
CAEF
Status
CA64
CA78
CA8C
CAA0
CAB4
CAC8
CADC
CAF0
Alarm status
CA65
CA79
CA8D
CAA1
CAB5
CAC9
CADD
CAF1
Note: The 14 registers must be written at once (as a group), otherwise it will respond with an
error.
225
Instruction Manual
CVM-B100 - CVM-B150