Impulse mode of transistor digital output
When selecting the impulse mode,
the configuration parameters are:
The variable code that controls the transistor.
The energy meter factor.
The high and low impulse period.
figure 132: Configuration screen of transistor digital outputs (impulse mode).
The parameter selected is indicated in white.
It is possible that the unit may measure energy exceeding its configuration. Make
sure the energy pulses correspond to the maximum energy level admitted by the
installation.
To program the transistor digital output, after configuring the
variable code and the pulse time
(with the
low period and high period parameters), the following formula provides a method for
calculating the number of output pulses according to the generated energy so that the pulses
do not accumulate.
3600 *
Pe / PT > MP → PE = MP * TP / 3600
Where:
MP : Maximum power of the installation in W.
Pe: Pulse energy in Wh ( energy meter factor )
TP : low period + high period, in seconds.
For example: If the installation can consume 100kW, a suitable configuration could be pulses
of 10W (
energy meter factor) with a high and low period of 50 ms.