Emergency broadcast, P. 94, Input. (refer to – Toa SX-2000 Series User Manual
Page 94: Control input. (refer to, Refer to

94
• Control input settings
Control input 1: Emergency broadcast pattern 1 start
Control input 2: Emergency broadcast pattern 2 start
Control input 3: Emergency broadcast pattern 3 start
Control input 4: Emergency broadcast pattern 1 stop
Control input 5: Emergency sequence 1 phase shift
Control input 6: Emergency sequence 1 stop
Control input 7: Emergency reset (EV5 playback)
EVENT SETTINGS
Function Description
12.2.6. Emergency broadcast
Emergency broadcast pattern can be started or stopped, sequence phase can be shifted within the pattern,
and emergency broadcast status can be reset to normal broadcast status via control input.
[Setting Example]
Perform settings for each item as follows in advance.
Note: Phase 3 is not set in this example.
EV message 1
Message name
EV1
Type
Alert
EV message 2
Message name
EV2
Type
Evacuation
EV message 4
Message name
EV4
Type
Evacuation
EV message 5
Message name
EV5
Type
Reset
EV message 3
Message name
EV3
Type
Alert
Phase 1
EV message 1, 5-minute broadcast
Phase 2
EV message 2, Continuous broadcast
Phase 3
Phase 1
EV message 3, 5-minute broadcast
Phase 2
EV message 4, Continuous broadcast
Phase 3
Phase 1
EV message 1,
5-minute broadcast
EV message 2,
Continuous broadcast
Output zone pattern 1
Output zone pattern 2
Phase 2
Phase 3
Control output pattern 1
Control output pattern 2
Emergency broadcast
pattern 1
Output zone
Control output
pattern
Phase 1
EV message 3,
5-minute broadcast
EV message 4,
Continuous broadcast
Output zone pattern 3
Output zone pattern 4
Phase 2
Phase 3
Control output pattern 3
Control output pattern 4
Emergency broadcast
pattern 2
Output zone
Control output
pattern
Phase 1
EV message 1,
5-minute broadcast
EV message 2,
Continuous broadcast
Output zone pattern 5
Output zone pattern 6
Phase 2
Phase 3
Control output pattern 5
Control output pattern 6
Emergency broadcast
pattern 3
Output zone
Control output
pattern
• EV message settings
• Emergency sequence settings
• Emergency broadcast pattern settings
Emergency
sequence 1
Emergency
sequence 1
Emergency
sequence 2
Emergency
sequence 1
Emergency
sequence 2