Emergency sequence settings, P. 82) – Toa SX-2000 Series User Manual
Page 82

82
PATTERN SETTINGS
Emergency Sequence Settings
11.5. Emergency Sequence Settings
Clicking the [Emergency sequence] button on the pattern settings screen allows Emergency sequences to be
set.
(1)
(2)
(3)
(1) Number
Click on the box or press the arrow button to select the emergency sequence number.
1 to 4 (default: 1)
Available Settings
(2) Name
Enter the name of the emergency sequence.
(4) Duration (min) (Phase 1)
Select the playback duration of the EV Message to be broadcast repeatedly.
Endless (default), 1 – 20 (minutes)
Available Settings
(4)
(3) Message (Phase 1)
Select the EV Message registered in the SX-2000SM
on the System Setting screen.
The selectable EV message type is "Alert" or "Evacuation."
The selected message type is displayed on the right of the message box.
None (default), Set EV messages
Available Settings
Note
To register the EV Message in Phases 2 and 3, "Duration" for the preceding phase should be set to a
limited time except "Continuous."
(5)
Up to 32 alphanumeric characters. (default: Emergency sequence 1 – 4)
Available Settings