PR 5230 Instrument Manual
Installing the Instrument and Plug-in Cards
Sartorius
EN-79
4.4.5.3
9-Pole D-Sub Connector ‚IN’
E.g. Phoenix Contact IBS RTC-T
Pin allocation acc. to
DIN 41642
Signal
Color
DIN 47100
Description
Cable sheath
green
special InterBus cable (certified)
1 -----------------------------
IDO1
green
inverted data output
2 -----------------------------
DO1
yellow
not inverted data output
3 -----------------------------
IDI1
pink
inverted data input
4 -----------------------------
DI1
grey
not inverted data input
5 -----------------------------
GND
brown
signal - ground
6 -----------------------------
S
Screen
4.4.5.4
9-Pole D-Sub Connector ‚OUT’
E.g. Phoenix Contact IBS RTC-T
Pin allocation acc. to
DIN 41642
Signal
Color
DIN 47100
Description
Cable sheath
green
special InterBus cable (certified)
7 -----------------------------
IDO2
green
inverted data output
8 -----------------------------
DO2
yellow
not inverted data output
9 -----------------------------
IDI2
pink
inverted data input
10 ----------------------------
DI2
grey
not inverted data input
11 --------- * only if necessary
GND
brown
signal - ground
(continuation jumper: 11-12)
12 --------- * only if necessary
C
Con_Test (continuation jumper: 11-12)
13 ----------------------------- S
Screen
4.4.5.5
Connecting Diagram for a Master with three Slaves
Caution!
With Bus OUT 11 and 12 must be bridged, if another slave follows. Thus the link is not
fitted at the last slave, see next page.
Caution!
The cable screens must be taken into the instrument through the cable glands and
connected to terminals 6 or 13 (see next page).
Before, during and after installation, make sure that the sealing rings are seated
correctly.