Installing the Instrument and Plug-in Cards

PR 5230 Instrument Manual

EN-74

Sartorius

4.4.4.1

Controls on Fieldbus Card

The terminating resistors can be switched on (ON) and off by pressing the
switch, see Chapter 4.4.4.4.



Caution!
The rotary switch settings will not use.
Make sure that the switches for mode address 1…99 are

set to position ‘0’!

The mode address will be set in the menu [Setup]-[Fieldbus Parameter].

4.4.4.2

Status-LEDs on Fieldbus Card

Watchdog LED

Meaning

Frequency

Color

Flashing

1 Hz green

Module is initialized and ready for operation.

Flashing

2 Hz green

Module is not initialized.

Flashing

1 Hz red

Check error in ASIC and FLASH ROM, module is defect.

4.4.4.3

Status Display

Requirements

In

-[Display items] the items are configured, see Chapter 5.6.7.

In

-[HW-Slots] PR 1721/41 is selected.

Display

1

2

3

4

LED ---

--- ---

---

1

2

3

4

Lit

- - -:

no function

Lit

grn:

Fieldbus is online, data
transmission is possible.

Flashing 1 Hz

red:

Input/output length
configuration error.

Lit

red:

Fieldbus is off-line, data
transmission is not possible.

Flashing 2 Hz

red:

User parameter error.

Flashing 4 Hz

red:

Error in ASIC

Legend

---

off

red

red

grn

green