Reading and writing register via fieldbus, Pr 5230 instrument manual fieldbus interface – Rice Lake PR5230 Fieldbus Transmitter User Manual
Page 193
![background image](/manuals/639397/193/background.png)
PR 5230 Instrument Manual
Fieldbus Interface
Sartorius
EN-193
Reading and Writing Register via Fieldbus
Reading Data: Read_Value, Read_Value_Select, Read_Value_Selected
When the master has to read from the instrument, the register number is transmitted in
Read_Value_Select
in the input area. The result is specified with
Read_Value_Selected in the output area
.
Action of the master
Response of PR 5230
Writing register no. in Read_Value_Select
Writing the selected register in Read_Value
Copying Read_Value_Select into
Read_Value_Selected
Waiting, until
Read_Value_Selected = Read_Value_Select
Reading Read_Value
Writing data: Write_Value, Write_Value_Select, Write_Active
When the master has to write into the instrument, the required action is transmitted into the input area with
Write_Value_Select
together with the data. Execution is indicated by bit
Write_Active
in the output area.
Action of the master
Response of PR 5230
Writing value in Write_Value
Writing the register number in Write_Value_Select
Writing Write_Value in the selected register
Setting bit Write_Active
Waiting, until Write_Active was set
Writing 0 in Write_Value_Select
Resetting bit Write_Active
Setting Bit: Action_Select, Write_Active
Single bits can be set or reset directly with
Write_Value_Select
.
For setting, the bit number (80.. 127) is written in
Write_Value_Select
.
For resetting, the bit number + 128 (208..255) is written in
Write_Value_Select
.
Action of the master
Response of PR 5230
Writing register number in Write_Value_Select
Writing Write_Value in the selected register
Setting the Write_Active bit
Waiting, until Write_Active was set.
Writing 0 in Write_Value_Select
Resetting the Write_Active bit