8 digital outputs and inputs, 1 configuring digital outputs, Digital outputs and inputs – Rice Lake PR5230 Fieldbus Transmitter User Manual
Page 154: Configuring digital outputs, Commissioning, Pr 5230 instrument manual
Commissioning
PR 5230 Instrument Manual
EN-154
Sartorius
5.8
Digital Outputs and Inputs
5.8.1
Configuring Digital Outputs
Configure the required function for [Output 1] to [Output 3] by selecting a signal from the list. The output goes
to the corresponding state, see Example.
Press
and select [Digital I/O parameter] to open the configuration menu.
Setup/
Digital I/O parameter
Output 1
below zero
X35=1
Output 2
above Max
X33=0
Output 3
center zero
X36=1
Input 1 on
-no action-
[Output 1] is true (active), when the weight value drops below zero (X35=1).
[Output 2] remains (active), as long as the weight is not above Max (X33=0).
[Output 3] is true (active), when the weight is zero ±¼ d (X36=1).
Selection list for output functions
Function
SPM bit
Description
actual diginp1
X00=0
Digital input 1: not active
actual diginp2
X01=0
Digital input 2: not active
actual diginp3
X02=0
Digital input 3: not active
actual limit 1
X16=0
Limit signal 1: not active
actual limit 2
X17=0
Limit signal 2: not active
actual limit 3
X18=0
Limit signal 3: not active
ADC error
X32=0
General error in the weighing point: not active (no error)
above Max
X33=0
Weight above Max: not active
overload
X34=0
Weight above Max plus the ‘overload’ value: not active
below zero
X35=0
Weight not below zero
center zero
X36=0
Weight not within ¼ d of zero
inside ZSR
X37=0
Weight not within zero-setting range
standstill
X38=0
No mechanical stability of the scale
out
X39=0
Weight not below zero or above Max
command error
X48=0
For internal use only.
command busy
X49=0
For internal use only.
power fail
X50=0
Set after power-on (=power failure): not active
test active
X56=0
Analog test was not started.
cal active
X57=0
For internal use only.
tare active
X58=0
Instrument is not tared.
marker bit 1
X64=0
Marker bit 1 not set, after power-on the markers are set to ‘0’.
marker bit 2
X65=0
Marker bit 2 not set, after power-on the markers are set to ‘0’.
marker bit 3
X66=0
Marker bit 3 not set, after power-on the markers are set to ‘0’.